Worked example
Example: 15 t/h for 24 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fly ash rate | 15.000 t/h |
| Storage time | 24.000 h |
| Bulk density in the silo | 750.00 kg/m³ |
| Usable fill fraction | 85.000 % |
| Cylinder height-to-diameter ratio | 1.5000 - |
| Moisture added for conditioning | 15.000 % |
| Unloading rate to trucks (dry ash) | 100.00 t/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Ash stored | 360.00 t |
| Silo volume (gross) | 564.71 m³ |
| Silo diameter | 7.8261 m |
| Cylinder height | 11.739 m |
| Conditioning water while unloading | 17.647 t/h |
Open this example in the calculator and change any input.
Formula
\(M = \dot m_at, \quad V = \frac{M}{\rho_bf}, \quad D = \sqrt[3]{\frac{4V}{\pi(H/D)}}, \quad H = (H/D)\,D, \quad \dot m_w = \dot m_{ul}\frac{w}{1 - w}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_a\) | Fly ash rate | kg/s |
| \(t\) | Storage time | s |
| \(\rho_b\) | Bulk density in the silo | kg/m³ |
| \(f\) | Usable fill fraction | - |
| \(H/D\) | Cylinder height-to-diameter ratio | - |
| \(w\) | Moisture added for conditioning | - |
| \(\dot m_{ul}\) | Unloading rate to trucks | kg/s |
| \(M\) | Ash stored | kg |
| \(V\) | Silo volume (gross) | m³ |
| \(D\) | Silo diameter | m |
| \(H\) | Cylinder height | m |
| \(\dot m_w\) | Conditioning water while unloading | kg/s |
Method and standards
Storage and moisture balance.
Where it is used
- Ash handling plant design.
- Checking silo capacity after a fuel change.
Common mistakes
- Using aerated density for storage.
- Forgetting moisture on a wet basis.
Assumptions and limits
- Cylinder section only: the whole gross volume is put in the cylinder, so a real silo with a hopper cone is a little smaller in cylinder height.
- The unloading rate is dry ash; the conditioning water is added on a wet basis.
References
- Volume and moisture balance definitions
Questions and answers
How many hours of storage?
Commonly 12–24 h of maximum ash rate, more where trucks do not run at night.
Why condition the ash?
Dry fly ash dusts badly; 10–20 % water in a conditioner (pug mill) lets it be trucked.
What do the defaults give?
15 t/h for 24 h: 360 t, about 565 m³ gross, a silo of about 7.8 m diameter and 11.7 m cylinder height.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.