Worked example
Example: Grate ash 500 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Ash discharged | 1.2000 t/h |
| Ash temperature | 500.00 °C |
| Ash temperature after quench | 60.000 °C |
| Ash specific heat | 0.83736 kJ/(kg·K) |
| Quench water temperature rise | 20.000 K |
| Share of the heat taken by evaporating water | 0 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat removed | 122.81 kW |
| Quench water | 5.2800 t/h |
| Water evaporated (lost as vapour, to make up) | 0 t/h |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m_a c_a (T_a - T_o)\)
\(\dot m_{ev} = \frac{f_{ev}\,\dot Q}{h_{fg}}, \quad \dot m_w = \frac{(1 - f_{ev})\,\dot Q}{c_w \Delta T_w} + \dot m_{ev}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_a\) | Ash discharged | kg/s |
| \(T_a\) | Ash temperature | K |
| \(T_o\) | Ash temperature after quench | K |
| \(c_a\) | Ash specific heat | J/(kg·K) |
| \(\Delta T_w\) | Quench water temperature rise | K |
| \(\dot Q\) | Heat removed | W |
| \(\dot m_w\) | Quench water | kg/s |
| \(f_{ev}\) | share of the heat taken by evaporating water | - |
| \(\dot m_{ev}\) | water evaporated, lost as vapour | kg/s |
| \(h_{fg}\) | latent heat of water at 101.325 kPa (IF97), about 2.257 | MJ/kg |
| \(c_w\) | specific heat of water, 4186.8 | J/(kg·K) |
Method and standards
Energy balance. Latent heat from FireCAD's IAPWS-IF97 at atmospheric pressure.
Where it is used
- Ash handling design.
Common mistakes
- Ash flow on fuel instead of discharged ash.
Assumptions and limits
- With \(f_{ev} = 0\) (the default) all the heat warms the water and none evaporates. Ash above 100 °C flashes some water; the evaporated share is your estimate, and the heat to bring that water to 100 °C is neglected.
- Ash specific heat is a constant 0.2 Btu/lb·°F; ASME PTC 4 gives a curve rising with temperature, so for bed ash at 800 °C and above the heat may be understated by some per cent.
References
- Energy balance; residue specific heat 0.2 Btu/lb·°F (837 J/kg·K, owner-confirmed default)
Questions and answers
Why 0.2 Btu/lb·°F?
A conventional residue specific heat used in boiler heat balances; enter a measured value if you have one.
Where does the heat go?
Into the quench water, which is cooled or evaporates.
Biomass ash?
Light and often unburnt: check for smouldering before conveying.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.