Cooling Water Pump Head for a Condenser and Tower Circuit

Total head and power of a cooling water pump from static lift to the tower distribution, pipe friction (Colebrook), condenser pressure drop and nozzle pressure.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 3,000 m³/h, 600 mm, 400 m, 12 m lift800 m³/h, 350 mm, 250 m

Results

Water viscosity taken as 0.8 mPa·s (about 30 °C). In an open tower circuit, the static lift is to the hot-water distribution level; the return falls back by gravity. Add margin for fouling and future plugging.

Pipe velocity2.9473m/s
Darcy friction factor0.012265
Pipe friction head3.6214m
Total pump head22.788m
Pump shaft power226.20kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3,000 m³/h, 600 mm, 400 m, 12 m lift. The inputs, in the units selected above:

InputValue
Water flow3,000.0 m³/h
Pipe inside diameter600.00 mm
Equivalent pipe length (pipe plus fittings)400.00 m
Pipe roughness0.045000 mm
Static lift (basin level to distribution)12.000 m
Condenser water-side pressure drop60.000 kPa
Pressure needed at the distribution nozzles10.000 kPa
Pump efficiency82.000 %
Water density996.00 kg/m³

Applying the formula below gives:

ResultValue
Pipe velocity2.9473 m/s
Darcy friction factor0.012265
Pipe friction head3.6214 m
Total pump head22.788 m
Pump shaft power226.20 kW

Open this example in the calculator and change any input.

Formula

\(H = H_s + f_D\frac{L_e}{D}\frac{V^2}{2g} + \frac{\Delta p_c + p_n}{\rho g}, \quad P = \frac{\rho gQH}{\eta}\)

\(V = \frac{4Q}{\pi D^2}, \quad Re = \frac{\rho V D}{\mu}, \quad \frac{1}{\sqrt{f_D}} = -2\log_{10}\left(\frac{\varepsilon/D}{3.7} + \frac{2.51}{Re\sqrt{f_D}}\right)\)

Variables

Symbol Meaning SI unit
\(Q\) Water flow m³/s
\(D\) Pipe inside diameter m
\(L_e\) Equivalent pipe length (pipe plus fittings) m
\(\varepsilon\) Pipe roughness m
\(H_s\) Static lift (basin level to distribution) m
\(\Delta p_c\) Condenser water-side pressure drop Pa
\(p_n\) Pressure needed at the distribution nozzles Pa
\(\eta\) Pump efficiency -
\(\rho\) Water density kg/m³
\(V\) Pipe velocity m/s
\(f_D\) Darcy friction factor -
\(Re\) Reynolds number -
\(\mu\) water viscosity, fixed at 0.8 mPa·s (about 30 °C) Pa·s
\(g\) standard gravity, 9.80665 m/s²
\(H_f\) Pipe friction head m
\(H\) Total pump head m
\(P\) Pump shaft power W

Method and standards

Darcy–Weisbach pipe friction with the Colebrook friction factor, plus the static lift and the condenser and nozzle pressure drops converted to head.

Where it is used

  • Cooling water pump selection.
  • Checking a circuit after adding a condenser.

Common mistakes

  • Counting the return leg as lift in an open circuit.
  • Ignoring condenser fouling margin.

Assumptions and limits

  • Single-phase water at about 30 °C: the viscosity is fixed at 0.8 mPa·s whatever density is entered. For much colder or warmer water the Reynolds number, and slightly the friction, differ.
  • Relative roughness ε/D up to 0.1, the range of the Colebrook equation; above it the input is rejected.

References

  • Darcy–Weisbach with the Colebrook friction factor (FireCAD engine) and static and component heads (definitions)

Questions and answers

What makes up the head?

Static lift to the tower distribution, pipe and fitting friction, the condenser's water-side drop and the nozzle pressure.

What velocity is usual?

2–3 m/s in large cooling water mains.

What do the defaults give?

3,000 m³/h in 600 mm pipe, 400 m equivalent, 12 m lift: about 23 m head and 226 kW.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.