Worked example
Example: Power plant tower 41 to 32 °C, wet bulb 27 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Hot water temperature (to tower) | 41.000 °C |
| Cold water temperature (from basin) | 32.000 °C |
| Ambient wet-bulb temperature | 27.000 °C |
| Water flow | 1.0800e+07 kg/h |
| Dry air flow | 9,720,000 kg/h |
| Atmospheric pressure | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Range | 9.0000 K |
| Approach to wet bulb | 5.0000 K |
| Effectiveness R/(R + A) | 64.286 % |
| Liquid-to-gas ratio | 1.1111 kg/kg |
| Heat rejected | 112.83 MW |
Open this example in the calculator and change any input.
Formula
\(R = T_{hot} - T_{cold} \qquad A = T_{cold} - T_{wb} \qquad \varepsilon = \frac{R}{R + A} \qquad \frac{L}{G} \qquad \dot Q = L\,\left[h(T_{hot}) - h(T_{cold})\right]\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_{hot}\) | hot water temperature | K |
| \(T_{cold}\) | cold water temperature | K |
| \(T_{wb}\) | ambient wet-bulb temperature | K |
| \(L\) | water flow | kg/s |
| \(G\) | dry air flow | kg/s |
| \(p\) | atmospheric pressure | Pa |
| \(R\) | range | K |
| \(A\) | approach | K |
| \(\varepsilon\) | effectiveness | – |
| \(L/G\) | liquid-to-gas ratio | kg/kg |
| \(\dot Q\) | heat rejected | W |
| \(h\) | water enthalpy | J/kg |
Method and standards
Range, approach and effectiveness as defined in cooling-tower practice (CTI terms; the BEE energy audit guide calls effectiveness "efficiency"); heat from water enthalpy by FireCAD's IAPWS-IF97.
Where it is used
- Cooling tower performance checks and energy audits.
- Comparing towers and seasons on the same basis.
- Spotting fill fouling or poor water distribution from a rising approach.
Common mistakes
- Using dry-bulb instead of wet-bulb temperature.
- Measuring the wet bulb close to the tower, in its own warm plume.
- Judging a tower by range alone: range follows the load, approach shows the tower.
Assumptions and limits
- Steady load; water loss by evaporation neglected in the heat balance.
- The air flow is used only for L/G; there is no air-side heat balance, so an L/G the air cannot support is not detected. Use the Merkel calculator to check the tower can do the duty.
References
- IAPWS R7-97(2012) IF97
- CTI and BEE cooling tower performance terms
Questions and answers
What are range and approach?
Range is how much the tower cools the water; approach is how close the cold water gets to the wet bulb. Water from 41 to 32 °C with a 27 °C wet bulb has a 9 K range and 5 K approach.
How is cooling tower effectiveness calculated?
Range over range plus approach: 9 / (9 + 5) = 64.3 %. Energy audit guides call this the cooling tower efficiency; compare it with the tower's design value rather than a fixed figure.
Why can't the water reach the wet bulb?
The driving force falls to zero as the water nears the wet bulb, so the last few kelvin need an ever larger tower. Approaches below about 3 K are rarely economic.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.