Worked example
Example: 35 MW, silica-limited. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat rejected | 35.000 MW |
| Silica in make-up (mg/L) | 20.000 - |
| Silica limit in circulating water (mg/L) | 150.00 - |
| Calcium hardness in make-up (mg/L as CaCO₃) | 120.00 - |
| Calcium hardness limit (mg/L as CaCO₃) | 600.00 - |
| Chloride in make-up (mg/L) | 50.000 - |
| Chloride limit (mg/L) | 500.00 - |
| TDS in make-up (mg/L) | 400.00 - |
| TDS limit (mg/L) | 2,500.0 - |
| Latent heat of evaporation | 2,410.0 kJ/kg |
| Drift as a share of evaporation | 0.20000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Allowed cycles of concentration | 5.0000 |
| Limiting species (1 silica, 2 hardness, 3 chloride, 4 TDS) | 2.0000 |
| Evaporation | 52.282 t/h |
| Blowdown (including drift) | 13.071 t/h |
| Make-up | 65.353 t/h |
| Deliberate blowdown (total less drift) | 12.966 t/h |
Open this example in the calculator and change any input.
Formula
\(N = \min_i\frac{C_{i,max}}{C_{i,mu}}, \quad E = \frac{Q}{h_{fg}}, \quad B = \frac{E}{N - 1}, \quad M = E + B, \quad B_d = B - d\,E\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Heat rejected | W |
| \(SiO_2\) | Silica in make-up (mg/L) | - |
| \(SiO_{2,max}\) | Silica limit in circulating water (mg/L) | - |
| \(CaH\) | Calcium hardness in make-up (mg/L as CaCO₃) | - |
| \(CaH_{max}\) | Calcium hardness limit (mg/L as CaCO₃) | - |
| \(Cl\) | Chloride in make-up (mg/L) | - |
| \(Cl_{max}\) | Chloride limit (mg/L) | - |
| \(TDS\) | TDS in make-up (mg/L) | - |
| \(TDS_{max}\) | TDS limit (mg/L) | - |
| \(h_{fg}\) | Latent heat of evaporation | J/kg |
| \(d\) | Drift as a share of evaporation | - |
| \(N\) | Allowed cycles of concentration | - |
| \(\text{limit}\) | Limiting species (1 silica, 2 hardness, 3 chloride, 4 TDS) | - |
| \(E\) | Evaporation | kg/s |
| \(B\) | Blowdown (including drift) | kg/s |
| \(M\) | Make-up | kg/s |
| \(B_d\) | deliberate blowdown, total solids-removing loss less drift | kg/s |
Method and standards
Mass balance on dissolved solids.
Where it is used
- Cooling water treatment programmes.
- Water conservation studies.
Common mistakes
- Ignoring drift and leaks as blowdown.
- Using limits without pH and temperature context.
Assumptions and limits
- Conservative species; all heat removed by evaporation, so evaporation, blowdown and make-up are higher (by about 18 % at the default) than in the cooling tower water balance calculator, which takes an evaporative share of 0.85.
- Drift here is a share of evaporation; the water balance calculator takes it as a share of circulating flow.
- The limiting species is shown as a number (1 silica, 2 hardness, 3 chloride, 4 TDS) and named in the note.
References
- Cooling tower mass balances: N = C_circulating/C_make-up
- B = E/(N − 1)
Questions and answers
Which limit usually governs?
It depends on the make-up water and the treatment: silica often governs high-silica waters, calcium hardness where scale inhibitors are weak. The default limits are illustrative; use your chemical supplier's values.
Why raise cycles?
Blowdown falls steeply: going from 3 to 6 cycles cuts blowdown by 60 %.
What do the defaults give?
Calcium hardness limits first, at 5 cycles (silica would allow 7.5): about 52 t/h evaporation for 35 MW and 13 t/h of blowdown.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.