Worked example
Example: Cooling water 4 K warmer. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Design heat load | 116.00 MW |
| Design CW inlet | 28.000 °C |
| Design CW outlet | 38.000 °C |
| Design condenser pressure (absolute) | 8.5000 kPa |
| New heat load | 116.00 MW |
| New CW inlet | 32.000 °C |
| CW flow ratio | 100.00 % |
| Share of tubes plugged | 0 % |
| Exponent of water velocity in U | 0.50000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| New saturation temperature | 46.665 °C |
| New condenser pressure | 10.446 kPa |
| New CW outlet | 42.000 °C |
| New NTU | 1.1454 |
| UA ratio | 1.0000 |
Open this example in the calculator and change any input.
Formula
Design point: \(\dot m_{w,d}c_p = \dfrac{Q_d}{t_{2,d} - t_{1,d}}\), \(NTU_d = \ln\dfrac{T_{s,d} - t_{1,d}}{T_{s,d} - t_{2,d}}\), \(UA_d = NTU_d\,\dot m_{w,d}c_p\), with \(T_{s,d} = T_{sat}(p_d)\) and \(t_2 = t_1 + Q/(\dot m_w c_p)\).
\(T_s = t_1 + \frac{Q}{\dot m_wc_p(1 - e^{-NTU})}, \quad NTU = \frac{UA}{\dot m_wc_p}, \quad \frac{UA}{UA_d} = (1 - f_{pl})\left(\frac{\dot m/\dot m_d}{1 - f_{pl}}\right)^n\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_d\) | Design heat load | W |
| \(t_{1,d}\) | Design CW inlet | K |
| \(t_{2,d}\) | Design CW outlet | K |
| \(p_d\) | Design condenser pressure (absolute) | Pa |
| \(Q\) | New heat load | W |
| \(t_1\) | New CW inlet | K |
| \(\dot m/\dot m_d\) | CW flow ratio | - |
| \(f_{pl}\) | Share of tubes plugged | - |
| \(n\) | Exponent of water velocity in U | - |
| \(T_s\) | New saturation temperature | K |
| \(p_c\) | New condenser pressure | Pa |
| \(t_2\) | New CW outlet | K |
| \(NTU\) | New NTU | - |
| \(UA/UA_d\) | UA ratio | - |
| \(\dot m_w c_p\), \(\dot m_{w,d}c_p\) | cooling water heat capacity rate, new and design | W/K |
| \(UA\), \(UA_d\) | overall conductance, new and design | W/K |
| \(NTU_d\) | design NTU | - |
| \(T_{s,d}\) | design saturation temperature | K |
Method and standards
Effectiveness–NTU model of a condenser (condensing side at one temperature), with \(UA\) back-calculated from the design point and scaled with the water velocity. Scaling the whole \(UA\) by velocity to the power \(n\) is a FireCAD simplification: \(n\) about 0.5 stands for the water film being part of the total resistance. It is not the HEI correction method.
Where it is used
- Summer–winter back pressure estimates.
- Effect of cooling tower or tube plugging on output.
Common mistakes
- Using the design load at part load.
- Forgetting air in-leakage effects.
Assumptions and limits
- Clean as at design; single pressure shell.
- Water specific heat and the effect of cooling water inlet temperature on \(U\) (which HEI corrects for) are not modelled; at colder water the true \(U\) is lower.
References
- Effectiveness–NTU for a condenser (C_r = 0) scaled from a design point; IAPWS-IF97 saturation
Questions and answers
Why does a warmer cooling water raise back pressure so much?
The saturation temperature must rise by about the same amount; each kelvin is about 0.39 kPa near 40 °C and 0.47 kPa near 45 °C.
What does plugging do?
It removes surface but raises water velocity in the remaining tubes, partly recovering U; the net UA falls about as √(1 − plugged share).
What do the defaults give?
The 8.5 kPa(a) design condenser with cooling water 4 K warmer runs at about 10.4 kPa(a).
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.