Worked example
Example: Two pumps in parallel, static 20 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Two pumps | In parallel |
| Pump shut-off head (zero flow) | 60.000 m |
| Rated flow | 100.00 m³/h |
| Head at rated flow | 50.000 m |
| Static head of the system | 20.000 m |
| A known flow of the system | 100.00 m³/h |
| Head the system needs at that flow | 50.000 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow with two pumps | 110.94 m³/h |
| Head with two pumps | 56.923 m |
| Flow through each pump | 55.470 m³/h |
| Flow gained over one pump | 10.940 % |
| Flow with one pump | 100.00 m³/h |
| Head with one pump | 50.000 m |
Open this example in the calculator and change any input.
Formula
Pump curve through the shut-off head and the rated point, system curve through the static head and a known point:
\(H_{pump} = H_0 - a\,Q^2,\ \ a = \frac{H_0 - H_r}{Q_r^2} \qquad H_{sys} = H_s + k\,Q^2,\ \ k = \frac{H_d - H_s}{Q_d^2}\)
\(Q_1 = \sqrt{\frac{H_0 - H_s}{a + k}} \qquad \text{parallel: } Q_2 = \sqrt{\frac{H_0 - H_s}{a/4 + k}} \qquad \text{series: } Q_2 = \sqrt{\frac{2H_0 - H_s}{2a + k}}\)
\(H_1 = H_s + k\,Q_1^2 \qquad H_2 = H_s + k\,Q_2^2 \qquad \Delta Q = \frac{Q_2}{Q_1} - 1\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{mode}\) | two pumps in parallel or in series | – |
| \(H_0\) | shut-off head of one pump | m |
| \(Q_r\) | rated flow of one pump | m³/s |
| \(H_r\) | head at rated flow | m |
| \(H_s\) | static head of the system | m |
| \(Q_d\) | a known flow of the system | m³/s |
| \(H_d\) | head the system needs at that flow | m |
| \(Q_2\) | flow with two pumps | m³/s |
| \(H_2\) | head with two pumps | m |
| \(Q_{each}\) | flow through each pump | m³/s |
| \(\Delta Q\) | flow gained over one pump | – |
| \(Q_1\) | flow with one pump | m³/s |
| \(H_1\) | head with one pump | m |
Method and standards
Intersection of the combined pump curve with the system curve, the method of Karassik's Pump Handbook: in parallel the flows add at equal head, in series the heads add at equal flow. Both curves are represented by parabolas through the points you enter.
Where it is used
- Combining pumps for flow or head.
- Standby and duty pump arrangements.
- Checking operating points with a system curve.
Common mistakes
- Assuming two parallel pumps give twice the flow on a steep system curve.
- Running mismatched pumps in parallel.
- Ignoring the second pump's NPSH in series.
Assumptions and limits
- Identical pumps; the parabola through shut-off and the rated point approximates the real curve near the rated point.
- System curve with constant static head and losses proportional to Q².
- Check that each pump in parallel stays above its minimum flow and each pump alone stays inside its curve.
References
- Karassik et al.
- Pump Handbook (parallel and series operation); ANSI/HI 1.3
Questions and answers
Do two pumps in parallel double the flow?
No. The system needs more head at more flow, so the second pump adds much less. With a pump of 60 m shut-off and 50 m at 100 m³/h on a system with 20 m static head, one pump gives 100 m³/h and two give 111 m³/h.
When does parallel operation pay?
When most of the system head is static. On a system that is all friction the gain is even smaller (7 % in the example).
When are pumps put in series?
When the system needs more head than one pump gives. Two in series on a 40 m static system deliver 163 m³/h against 100 m³/h for one pump.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.