Worked example
Example: 100 m³/h, 5 bar g / 0.3 bar g, 22 kW input, motor 92 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Measured flow | 100.00 m³/h |
| Discharge pressure | 5.0000 bar g |
| Suction pressure | 0.30000 bar g |
| Height of the discharge gauge above the suction gauge | 0.50000 m |
| Suction pipe inside diameter at the gauge | 150.00 mm |
| Discharge pipe inside diameter at the gauge | 100.00 mm |
| Liquid density | 998.00 kg/m³ |
| Motor input power (measured) | 22.000 kW |
| Motor efficiency at this load | 92.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pump total head | 49.034 m |
| Hydraulic power | 13.331 kW |
| Pump shaft power | 20.240 kW |
| Pump efficiency | 65.863 % |
| Overall (wire-to-water) efficiency | 60.594 % |
Open this example in the calculator and change any input.
Formula
\(H = \frac{p_d - p_s}{\rho g} + \Delta z + \frac{v_d^2 - v_s^2}{2g}\)
\(P_h = \rho g Q H, \quad P_{sh} = P_{in} \eta_m\)
\(\eta_p = P_h / P_{sh}, \quad \eta_o = P_h / P_{in}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | flow | m³/s |
| \(p_d\) | discharge pressure | Pa |
| \(p_s\) | suction pressure | Pa |
| \(\Delta z\) | height of discharge gauge above suction gauge | m |
| \(D_s\) | suction pipe diameter | m |
| \(D_d\) | discharge pipe diameter | m |
| \(\rho\) | liquid density | kg/m³ |
| \(P_{in}\) | motor input power | W |
| \(\eta_m\) | motor efficiency | - |
| \(v_s\) | suction velocity | m/s |
| \(v_d\) | discharge velocity | m/s |
| \(g\) | standard gravity | m/s² |
| \(H\) | total head | m |
| \(P_h\) | hydraulic power | W |
| \(P_{sh}\) | shaft power | W |
| \(\eta_p\) | pump efficiency | - |
| \(\eta_o\) | overall efficiency | - |
Method and standards
Total head is the rise in pressure head plus the gauge height difference and the velocity heads at the gauge points. Hydraulic power over shaft power (motor input times motor efficiency) gives the pump efficiency.
Where it is used
- Energy audits of pumping systems.
- Checking pump wear and deciding on overhaul.
- Verifying commissioning performance.
Common mistakes
- Gauges at different heights without the Δz correction.
- Using a clamp-on flow reading without checking its accuracy.
- Taking the nameplate motor efficiency at part load.
Assumptions and limits
- Steady flow; incompressible liquid; gauges calibrated.
References
- Pump total head from gauge readings (pressure, elevation and velocity heads, the definition used in ISO 9906 acceptance tests); hydraulic power ρ g Q H
Questions and answers
How efficient is a pump giving 100 m³/h against 5 bar g discharge and 0.3 bar g suction on 22 kW input?
Head about 49 m; hydraulic power 13.3 kW; with a 92 % motor the pump is about 66 % efficient and the set about 61 %.
Why include velocity heads?
When suction and discharge pipes differ in size, the faster discharge velocity is part of the head the pump adds.
What if the pump efficiency comes out too low?
Compare with the maker's curve at the same flow: wear, recirculation or a wrong operating point are common causes.