Sensor Time Constant, Step Response and Ramp Lag

Response of a first-order sensor such as a thermocouple in a thermowell: reading after a step change, times to 63, 90, 95 and 99 %, and the lag behind a steady ramp.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Bare thermocouple, 10 s: 100 K step, after 30 s, 5 K/min rampThermowell, 60 s: 50 K step after 60 s, 2 K/minRTD, 4 s: -20 K step after 2 s, no ramp

Results

First-order model: one time constant gives 63.2 % of a step. A sensor in a thermowell often behaves as two lags in series, which is slower at the start.

Share of the step shown at time t: 1 − e^(−t/τ)95.021%
Change shown by the sensor at time t95.021K
Error left at time t4.9787K
Time to 90 % of the step23.026s
Time to 95 %29.957s
Time to 99 %46.052s
Steady lag behind a ramp r τ0.83333K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Bare thermocouple, 10 s: 100 K step, after 30 s, 5 K/min ramp. The inputs, in the units selected above:

InputValue
Time constant of the sensor10.000 s
Size of the step change100.00 K
Time after the step30.000 s
Rate of a steady ramp5.0000 °C/min

Applying the formula below gives:

ResultValue
Share of the step shown at time t: 1 − e^(−t/τ)95.021 %
Change shown by the sensor at time t95.021 K
Error left at time t4.9787 K
Time to 90 % of the step23.026 s
Time to 95 %29.957 s
Time to 99 %46.052 s
Steady lag behind a ramp r τ0.83333 K

Open this example in the calculator and change any input.

Formula

\(f = 1 - e^{-t/\tau}, \quad t_x = -\tau \ln(1 - x)\)

\(e_r = r\,\tau\)

Variables

Symbol Meaning SI unit
\(\tau\) Time constant of the sensor s
\(\Delta T\) Size of the step change K
\(t\) Time after the step s
\(r\) Rate of a steady ramp K/s
\(f\) Share of the step shown at time t: 1 − e^(−t/τ) -
\(\Delta T_r\) Change shown by the sensor at time t K
\(e\) Error left at time t K
\(t_{90}\) Time to 90 % of the step s
\(t_{95}\) Time to 95 % s
\(t_{99}\) Time to 99 % s
\(e_r\) Steady lag behind a ramp r τ K

Method and standards

Solution of the first-order equation τ dT_s/dt + T_s = T for a step and a ramp.

Where it is used

  • Choosing sensors for fast loops.
  • Explaining reading lag during boiler start-up.
  • Control loop tuning.

Common mistakes

  • Confusing the time constant with the 99 % time.
  • Testing in still air and using the value in flowing water.

Assumptions and limits

  • First-order response.

References

  • First-order system step and ramp response (control theory)

Questions and answers

How long does a 10 s sensor take to show 99 % of a step?

46 s (4.6 time constants). After 30 s it shows 95 %.

How far behind a 5 °C/min ramp does it read?

0.83 °C: the rate times the time constant.

Why is a thermowell slower?

The extra mass and air gap add lag; time constants of a minute or more are common.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.