Flowmeter K-Factor and Meter Factor from a Proving Run

K-factor and meter factor of a pulse flowmeter from a proving or calibration run: pulses counted, true volume from the prover or tank, and indicated volume.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 50 120 pulses for 5 m³ at K 10 000/m³9 950 pulses for 1 m³ at K 10 0002 000 pulses for 0.5 m³ at K 4 000

Results

Measured K-factor (pulses per m³)9,950.0
Volume indicated by the meter0.99500m³
Meter factor (true / indicated)1.0050
Meter error (indicated − true) / true-0.50000%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 50 120 pulses for 5 m³ at K 10 000/m³. The inputs, in the units selected above:

InputValue
Pulses counted in the run50,120 -
True volume (prover or tank)5.0000 m³
K-factor programmed in the meter, in pulses per m³ (per litre × 1000; per US gal × 264.17)10,000 -

Applying the formula below gives:

ResultValue
Measured K-factor (pulses per m³)10,024
Volume indicated by the meter5.0120 m³
Meter factor (true / indicated)0.99761
Meter error (indicated − true) / true0.24000 %

Open this example in the calculator and change any input.

Formula

\(K = \frac{N}{V_t}, \quad V_i = \frac{N}{K_0}, \quad MF = \frac{V_t}{V_i}\)

Variables

Symbol Meaning SI unit
\(N\) Pulses counted in the run -
\(V_t\) True volume (prover or tank) m³
\(K_0\) K-factor programmed in the meter (pulses per m³) -
\(K\) Measured K-factor (pulses per m³) -
\(V_i\) Volume indicated by the meter m³
\(MF\) Meter factor (true / indicated) -
\(\varepsilon\) Meter error (indicated − true) / true -

Method and standards

Definitions.

Where it is used

  • Meter calibration and custody transfer.
  • Tank-strapping checks.

Common mistakes

  • Mixing per litre and per m³.
  • Too few pulses.

Assumptions and limits

  • Steady flow during the run.
  • No temperature and pressure corrections (CTL, CPL) of the prover and meter volumes as in API MPMS proving; for liquids away from reference conditions apply them first.
  • K-factors in pulses per m³: multiply a per-litre figure by 1 000 or a per-US-gallon figure by 264.17.

References

  • Meter factor MF = true volume / indicated volume (API MPMS ch. 4 terminology)

Questions and answers

50 120 pulses for 5 m³ on a meter set to 10 000/m³?

K = 10 024/m³; the meter shows 5.012 m³, reading 0.24 % high; meter factor 0.9976.

Change K or apply a meter factor?

Either; custody transfer usually keeps K and applies the factor.

How many pulses per run?

At least 10 000 so one pulse is 0.01 %.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.