Flowmeter Pulse Output and Totaliser Scaling (K-Factor)

K-factor and pulse frequency of a flowmeter's pulse output at maximum flow, the divider needed to stay within a counter's input limit, and the scaled volume per pulse.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPump

Inputs

Examples: 1 L per pulse, 50 m³/h, 10 Hz input0.1 L per pulse, 120 m³/h, 100 Hz10 L per pulse, 20 m³/h, 5 Hz (no divider)

Results

Keep some margin below the input limit, and check the pulse width as well as the rate: slow PLC inputs miss short pulses.

K-factor (pulses per m³)100.00
Pulse frequency at maximum flow0.55556Hz
Smallest pulse divider within the limit (whole number, no margin)1.0000
Volume per pulse after the divider10.000L
Pulse frequency after the divider0.55556Hz
Pulses per day at maximum flow (after the divider)48,000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 L per pulse, 50 m³/h, 10 Hz input. The inputs, in the units selected above:

InputValue
Volume per pulse from the meter1.0000 L
Maximum flow50.000 m³/h
Highest pulse rate the counter or PLC input accepts10.000 Hz

Applying the formula below gives:

ResultValue
K-factor (pulses per m³)1,000.0
Pulse frequency at maximum flow13.889 Hz
Smallest pulse divider within the limit (whole number, no margin)2.0000
Volume per pulse after the divider2.0000 L
Pulse frequency after the divider6.9444 Hz
Pulses per day at maximum flow (after the divider)600,000

Open this example in the calculator and change any input.

Formula

\(K = \frac{1}{V_p}, \quad f = \frac{Q}{V_p}, \quad n = \left\lceil \frac{f}{f_{lim}} \right\rceil\)

Variables

Symbol Meaning SI unit
\(V_p\) Volume per pulse from the meter m³
\(Q_{max}\) Maximum flow m³/s
\(f_{lim}\) Highest pulse rate the counter or PLC input accepts 1/s
\(K\) K-factor (pulses per m³) -
\(f_{max}\) Pulse frequency at maximum flow 1/s
\(n\) Smallest pulse divider within the limit (whole number, no margin) -
\(V_{p,out}\) Volume per pulse after the divider m³
\(f_{out}\) Pulse frequency after the divider 1/s
\(N_d\) Pulses per day at maximum flow (after the divider) -

Method and standards

Pulse rate equals flow divided by volume per pulse.

Where it is used

  • Configuring meters and PLCs.
  • Totaliser checks.

Common mistakes

  • Units of K mixed (per L vs per m³).
  • No margin below the input limit.

Assumptions and limits

  • Constant K-factor.
  • The divider is the smallest that keeps the pulse rate at or below the limit, with no margin: choose a larger one for margin. Pulse width and duty cycle are not computed; check them against the input's minimum on-time.

References

  • Pulse output relations f = Q/V_p

Questions and answers

What pulse rate does a 1 L/pulse meter give at 50 m³/h?

13.9 Hz, above a 10 Hz PLC input: divide by 2 for 2 L per pulse at 6.9 Hz.

What is the K-factor?

Pulses per unit volume: 1000 per m³ here.

Why check pulse width?

Slow inputs miss short pulses even below their rate limit.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.