Worked example
Example: 1 L per pulse, 50 m³/h, 10 Hz input. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Volume per pulse from the meter | 1.0000 L |
| Maximum flow | 50.000 m³/h |
| Highest pulse rate the counter or PLC input accepts | 10.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| K-factor (pulses per m³) | 1,000.0 |
| Pulse frequency at maximum flow | 13.889 Hz |
| Smallest pulse divider within the limit (whole number, no margin) | 2.0000 |
| Volume per pulse after the divider | 2.0000 L |
| Pulse frequency after the divider | 6.9444 Hz |
| Pulses per day at maximum flow (after the divider) | 600,000 |
Open this example in the calculator and change any input.
Formula
\(K = \frac{1}{V_p}, \quad f = \frac{Q}{V_p}, \quad n = \left\lceil \frac{f}{f_{lim}} \right\rceil\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_p\) | Volume per pulse from the meter | m³ |
| \(Q_{max}\) | Maximum flow | m³/s |
| \(f_{lim}\) | Highest pulse rate the counter or PLC input accepts | 1/s |
| \(K\) | K-factor (pulses per m³) | - |
| \(f_{max}\) | Pulse frequency at maximum flow | 1/s |
| \(n\) | Smallest pulse divider within the limit (whole number, no margin) | - |
| \(V_{p,out}\) | Volume per pulse after the divider | m³ |
| \(f_{out}\) | Pulse frequency after the divider | 1/s |
| \(N_d\) | Pulses per day at maximum flow (after the divider) | - |
Method and standards
Pulse rate equals flow divided by volume per pulse.
Where it is used
- Configuring meters and PLCs.
- Totaliser checks.
Common mistakes
- Units of K mixed (per L vs per m³).
- No margin below the input limit.
Assumptions and limits
- Constant K-factor.
- The divider is the smallest that keeps the pulse rate at or below the limit, with no margin: choose a larger one for margin. Pulse width and duty cycle are not computed; check them against the input's minimum on-time.
References
- Pulse output relations f = Q/V_p
Questions and answers
What pulse rate does a 1 L/pulse meter give at 50 m³/h?
13.9 Hz, above a 10 Hz PLC input: divide by 2 for 2 L per pulse at 6.9 Hz.
What is the K-factor?
Pulses per unit volume: 1000 per m³ here.
Why check pulse width?
Slow inputs miss short pulses even below their rate limit.