Worked example
Example: wn 0.5 rad/s, zeta 0.4, 2 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Natural frequency ω_n in rad/s | 0.50000 1/s |
| Damping ratio | 0.40000 - |
| Settling band | 2.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Overshoot | 25.383 % |
| Time to the first peak | 6.8555 s |
| Settling time (envelope) | 19.996 s |
| Rise time 0–100 % | 4.3258 s |
| Damped frequency ω_d in rad/s | 0.45826 1/s |
Open this example in the calculator and change any input.
Formula
\(M_p = e^{-\zeta\pi/\sqrt{1-\zeta^2}}, \quad t_p = \frac{\pi}{\omega_d}, \quad t_s = \frac{-\ln(\epsilon\sqrt{1-\zeta^2})}{\zeta\omega_n}, \quad \omega_d = \omega_n\sqrt{1-\zeta^2}, \quad t_r = \frac{\pi - \arccos\zeta}{\omega_d}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\omega_n\) | Natural (angular) frequency | rad/s |
| \(\zeta\) | Damping ratio | - |
| \(\epsilon\) | Settling band | - |
| \(M_p\) | Overshoot | - |
| \(t_p\) | Time to the first peak | s |
| \(t_s\) | Settling time (envelope) | s |
| \(t_r\) | Rise time 0–100 % | s |
| \(\omega_d\) | Damped (angular) frequency | rad/s |
Method and standards
Analytic step response.
Where it is used
- Loop performance specification.
- Control examinations.
Common mistakes
- Hz instead of rad/s.
- Applying to non-second-order loops.
Assumptions and limits
- Underdamped, no zeros.
- ω_n and ω_d are angular frequencies in rad/s (shown as 1/s); a natural frequency in Hz must be multiplied by 2π first.
References
- Standard second-order response (Ogata, Modern Control Engineering, ch. 5)
Questions and answers
What overshoot does ζ = 0.4 give?
25.4 %.
How long to settle within 2 % with ω_n = 0.5 rad/s?
20.0 s by the envelope (about 4/(ζω_n) = 20 s).
What damping is usual for loops?
0.4 to 0.7; quarter decay corresponds to about 0.22.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.