PID Tuning by Ziegler–Nichols (Ultimate Gain)

Starting P, PI and PID controller settings from the ultimate gain and ultimate period found in a closed-loop test, by the Ziegler–Nichols rules.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserBoiler

Inputs

Examples: Drum level: Ku 4, Tu 60 sSteam pressure: Ku 2.5, Tu 120 sFurnace draught: Ku 1.2, Tu 8 s

Results

Ziegler–Nichols settings are aggressive (quarter-amplitude decay); reduce the gain for smoother boiler loops. Gain here is dimensionless (% output per % input); convert from proportional band if your controller uses it.

PID: proportional gain0.72000
PID: integral time4.0000s
PID: derivative time1.0000s
PI: proportional gain0.54000
PI: integral time6.6667s
P only: proportional gain0.60000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Drum level: Ku 4, Tu 60 s. The inputs, in the units selected above:

InputValue
Ultimate gain (gain at steady oscillation)4.0000 -
Ultimate period of the oscillation60.000 s

Applying the formula below gives:

ResultValue
PID: proportional gain2.4000
PID: integral time30.000 s
PID: derivative time7.5000 s
PI: proportional gain1.8000
PI: integral time50.000 s
P only: proportional gain2.0000

Open this example in the calculator and change any input.

Formula

\(P: K_p = 0.5 K_u \qquad PI: K_p = 0.45 K_u,\ T_i = T_u/1.2 \qquad PID: K_p = 0.6 K_u,\ T_i = T_u/2,\ T_d = T_u/8\)

Variables

Symbol Meaning SI unit
\(K_u\) ultimate gain –
\(T_u\) ultimate period s
\(K_{p,PID}\) PID gain –
\(T_{i,PID}\) PID integral time s
\(T_{d,PID}\) PID derivative time s
\(K_{p,PI}\) PI gain –
\(T_{i,PI}\) PI integral time s
\(K_{p,P}\) P-only gain –
\(K_p, T_i, T_d\) gain, integral and derivative time in general –, s, s

Method and standards

Ziegler and Nichols (1942) closed-loop (ultimate sensitivity) rules for an ideal (standard) PID form.

Where it is used

  • Commissioning drum level, pressure, temperature and draught loops.
  • First settings for new loops.
  • Teaching control tuning.

Common mistakes

  • Using the settings unchanged on interacting or series-form controllers.
  • Mixing gain and proportional band.
  • Tuning with valves at their limits.

Assumptions and limits

  • Ideal PID form; linear process near the operating point.

References

  • J.G. Ziegler and N.B. Nichols (1942)

Questions and answers

How do I tune a loop by Ziegler–Nichols?

With integral and derivative off, raise the gain until the loop oscillates steadily: that gain is Ku and the period Tu. With Ku = 4 and Tu = 60 s, a PID gets Kp 2.4, Ti 30 s, Td 7.5 s; a PI gets 1.8 and 50 s.

Are these final settings?

No: Ziegler–Nichols gives quarter-amplitude decay, often too lively for boiler loops; reduce the gain and lengthen the integral for smoother control.

Is it safe to make a boiler loop oscillate?

Only with care, small amplitudes and operator agreement; drum level and furnace pressure loops have trips close by.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.