Worked example
Example: Series 2, 60 s, 10 s → ideal. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Conversion | Series → ideal |
| Controller gain | 2.0000 - |
| Integral time | 60.000 s |
| Derivative time | 10.000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Converted gain | 2.3333 |
| Converted integral time | 70.000 s |
| Converted derivative time | 8.5714 s |
| Realisable (1 = yes) | 1.0000 |
Open this example in the calculator and change any input.
Formula
Unprimed values are the settings entered; primed values are the converted settings.
\(K_c' = K_c\left(1 + \frac{T_d}{T_i}\right), \ T_i' = T_i + T_d, \ T_d' = \frac{T_iT_d}{T_i + T_d}\ \text{(series → ideal)}\)
\(r = \sqrt{1 - \frac{4T_d}{T_i}}, \ K_c' = K_c\frac{1 + r}{2}, \ T_i' = T_i\frac{1 + r}{2}, \ T_d' = T_i\frac{1 - r}{2}\ \text{(ideal → series; needs } T_i \ge 4T_d)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{direction}\) | Conversion | - |
| \(K_c\) | Controller gain | - |
| \(T_i\) | Integral time | s |
| \(T_d\) | Derivative time | s |
| \(K_c'\) | Converted gain | - |
| \(T_i'\) | Converted integral time | s |
| \(T_d'\) | Converted derivative time | s |
| \(\text{realisable}\) | Realisable (1 = yes) | - |
Method and standards
PID algebra.
Where it is used
- Moving tuning between DCS platforms.
- Applying textbook tuning rules.
Common mistakes
- Ignoring the form difference with derivative on.
- Converting gain in % vs. engineering units.
Assumptions and limits
- No filter on derivative.
- Ideal settings with T_i < 4T_d have no series equivalent: only "realisable = 0" is shown.
References
- Seborg
- Edgar
- Mellichamp and Doyle
- Process Dynamics and Control
- 4th ed. (Wiley, 2016)
- ch. 8 (PID forms and conversion)
Questions and answers
Why does the form matter?
The same three numbers give different behaviour in series and ideal controllers when derivative is used; tuning rules assume one form.
When can ideal not be converted?
When T_i is less than four times T_d: the ideal controller then has complex zeros the series form cannot produce.
What do the defaults represent?
Series settings K_c = 2, T_i = 60 s, T_d = 10 s.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.