FireCADCalc

PID Tuning Conversion: Series (Interacting) and Ideal Forms

Convert PID settings between the series (interacting) form of many DCS and the ideal ISA form, and check that ideal settings are realisable.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Series 2, 60 s, 10 s → idealIdeal 2.33, 70 s, 8.57 s → series

Results

Converted gain2.0000
Converted integral time60.000s
Converted derivative time10.000s
Realisable (1 = yes)1.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Series 2, 60 s, 10 s → ideal. The inputs, in the units selected above:

InputValue
ConversionSeries → ideal
Controller gain2.0000 -
Integral time60.000 s
Derivative time10.000 s

Applying the formula below gives:

ResultValue
Converted gain2.3333
Converted integral time70.000 s
Converted derivative time8.5714 s
Realisable (1 = yes)1.0000

Open this example in the calculator and change any input.

Formula

Unprimed values are the settings entered; primed values are the converted settings.

\(K_c' = K_c\left(1 + \frac{T_d}{T_i}\right), \ T_i' = T_i + T_d, \ T_d' = \frac{T_iT_d}{T_i + T_d}\ \text{(series → ideal)}\)

\(r = \sqrt{1 - \frac{4T_d}{T_i}}, \ K_c' = K_c\frac{1 + r}{2}, \ T_i' = T_i\frac{1 + r}{2}, \ T_d' = T_i\frac{1 - r}{2}\ \text{(ideal → series; needs } T_i \ge 4T_d)\)

Variables

Symbol Meaning SI unit
\(\text{direction}\) Conversion -
\(K_c\) Controller gain -
\(T_i\) Integral time s
\(T_d\) Derivative time s
\(K_c'\) Converted gain -
\(T_i'\) Converted integral time s
\(T_d'\) Converted derivative time s
\(\text{realisable}\) Realisable (1 = yes) -

Method and standards

PID algebra.

Where it is used

  • Moving tuning between DCS platforms.
  • Applying textbook tuning rules.

Common mistakes

  • Ignoring the form difference with derivative on.
  • Converting gain in % vs. engineering units.

Assumptions and limits

  • No filter on derivative.
  • Ideal settings with T_i < 4T_d have no series equivalent: only "realisable = 0" is shown.

References

  • Seborg
  • Edgar
  • Mellichamp and Doyle
  • Process Dynamics and Control
  • 4th ed. (Wiley, 2016)
  • ch. 8 (PID forms and conversion)

Questions and answers

Why does the form matter?

The same three numbers give different behaviour in series and ideal controllers when derivative is used; tuning rules assume one form.

When can ideal not be converted?

When T_i is less than four times T_d: the ideal controller then has complex zeros the series form cannot produce.

What do the defaults represent?

Series settings K_c = 2, T_i = 60 s, T_d = 10 s.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.