Lambda (IMC) Tuning for PI Controllers

PI controller gain and integral time by lambda tuning for a self-regulating first-order plus dead-time process, from the closed-loop time constant λ.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Gain 2, 60 s, 10 s, lambda 90 sConsistency loop: gain 1.5, 30 s, 5 s, lambda 30 sLevel-like: gain 0.4, 300 s, 20 s, lambda 600 s

Often 1 to 3 times the process time constant; larger is more robust.

Results

No overshoot to a set-point step when the model is right; choose λ to coordinate interacting loops.

Controller gain0.57143
Integral time (= τ)30.000s
Speed ratio λ/τ (1 = same speed as open loop)1.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Gain 2, 60 s, 10 s, lambda 90 s. The inputs, in the units selected above:

InputValue
Process gain (change in output / change in controller output)2.0000 -
Process time constant60.000 s
Dead time10.000 s
Closed-loop time constant λ90.000 s

Applying the formula below gives:

ResultValue
Controller gain0.30000
Integral time (= τ)60.000 s
Speed ratio λ/τ (1 = same speed as open loop)1.5000

Open this example in the calculator and change any input.

Formula

\(K_c = \frac{\tau}{K_p(\lambda + \theta)}, \quad T_i = \tau\)

Variables

Symbol Meaning SI unit
\(K_p\) Process gain (change in output / change in controller output) -
\(\tau\) Process time constant s
\(\theta\) Dead time s
\(\lambda\) Closed-loop time constant λ s
\(K_c\) Controller gain -
\(T_i\) Integral time (= τ) s
\(\lambda/\tau\) Speed ratio λ/τ (1 = same speed as open loop) -

Method and standards

Internal model control design.

Where it is used

  • Pulp and paper and process plants.
  • Coordinated loop tuning.

Common mistakes

  • λ shorter than the dead time.
  • Using it on integrating processes.

Assumptions and limits

  • First-order plus dead time.

References

  • Lambda tuning (Dahlin 1968; IMC, Rivera, Morari and Skogestad 1986)

Questions and answers

Gain 2, τ 60 s, θ 10 s, λ 90 s: what settings?

K_c = 60/(2 × 100) = 0.3, T_i = 60 s.

How is λ chosen?

Slower than the dead time; tighter loops get a smaller λ, interacting loops different λ.

How does SIMC differ?

SIMC caps the integral time for slow processes; lambda keeps T_i = τ.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.