FireCADCalc

Step Test Model: Gain, Time Constant and Dead Time (Two-Point Method)

Process gain, time constant and dead time of a first-order plus dead-time model from a step test by Smith's two-point method (28.3 % and 63.2 % times).

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 10 % step, 20 % change, 30 s and 70 s5 % step, −7.5 % change (reverse acting), 12 s and 25 s2 % step, 10 °C, 150 s and 450 s

Results

Express Δu and Δy in the same units (usually % of range) so the gain is dimensionless.

Process gain Δy / Δu5.0000
Time constant 1.5 (t₆₃ − t₂₈)450.00s
Dead time t₆₃ − τ0s
Controllability ratio θ/τ0

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 % step, 20 % change, 30 s and 70 s. The inputs, in the units selected above:

InputValue
Step in controller output10.000 -
Final change in the measured variable20.000 -
Time to 28.3 % of the change (from the step)30.000 s
Time to 63.2 % of the change70.000 s

Applying the formula below gives:

ResultValue
Process gain Δy / Δu2.0000
Time constant 1.5 (t₆₃ − t₂₈)60.000 s
Dead time t₆₃ − τ10.000 s
Controllability ratio θ/τ0.16667

Open this example in the calculator and change any input.

Formula

\(\tau = 1.5\,(t_{63} - t_{28}), \quad \theta = t_{63} - \tau, \quad K_p = \frac{\Delta y}{\Delta u}\)

Variables

Symbol Meaning SI unit
\(\Delta u\) Step in controller output -
\(\Delta y\) Final change in the measured variable -
\(t_{28}\) Time to 28.3 % of the change (from the step) s
\(t_{63}\) Time to 63.2 % of the change s
\(K_p\) Process gain Δy / Δu -
\(\tau\) Time constant 1.5 (t₆₃ − t₂₈) s
\(\theta\) Dead time t₆₃ − τ s
\(\theta/\tau\) Controllability ratio θ/τ -

Method and standards

Two points on the first-order step response.

Where it is used

  • Loop tuning.
  • Process modelling.

Common mistakes

  • Timing from the wrong start.
  • Noisy data near the end.

Assumptions and limits

  • Self-regulating response.

References

  • C.L. Smith
  • Digital Computer Process Control (1972)
  • two-point method

Questions and answers

A 10 % step gives a 20 % change, reaching 28.3 % at 30 s and 63.2 % at 70 s. What model?

Gain 2, τ = 1.5 × 40 = 60 s, θ = 70 − 60 = 10 s.

Why 28.3 and 63.2 %?

They are θ + τ/3 and θ + τ on a first-order curve.

What is a hard process?

θ/τ above about 1: dead time dominates.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators