Worked example
Example: 10 % step, 20 % change, 30 s and 70 s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Step in controller output | 10.000 - |
| Final change in the measured variable | 20.000 - |
| Time to 28.3 % of the change (from the step) | 30.000 s |
| Time to 63.2 % of the change | 70.000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Process gain Δy / Δu | 2.0000 |
| Time constant 1.5 (t₆₃ − t₂₈) | 60.000 s |
| Dead time t₆₃ − τ | 10.000 s |
| Controllability ratio θ/τ | 0.16667 |
Open this example in the calculator and change any input.
Formula
\(\tau = 1.5\,(t_{63} - t_{28}), \quad \theta = t_{63} - \tau, \quad K_p = \frac{\Delta y}{\Delta u}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\Delta u\) | Step in controller output | - |
| \(\Delta y\) | Final change in the measured variable | - |
| \(t_{28}\) | Time to 28.3 % of the change (from the step) | s |
| \(t_{63}\) | Time to 63.2 % of the change | s |
| \(K_p\) | Process gain Δy / Δu | - |
| \(\tau\) | Time constant 1.5 (t₆₃ − t₂₈) | s |
| \(\theta\) | Dead time t₆₃ − τ | s |
| \(\theta/\tau\) | Controllability ratio θ/τ | - |
Method and standards
Two points on the first-order step response.
Where it is used
- Loop tuning.
- Process modelling.
Common mistakes
- Timing from the wrong start.
- Noisy data near the end.
Assumptions and limits
- Self-regulating response.
References
- C.L. Smith
- Digital Computer Process Control (1972)
- two-point method
Questions and answers
A 10 % step gives a 20 % change, reaching 28.3 % at 30 s and 63.2 % at 70 s. What model?
Gain 2, τ = 1.5 × 40 = 60 s, θ = 70 − 60 = 10 s.
Why 28.3 and 63.2 %?
They are θ + τ/3 and θ + τ on a first-order curve.
What is a hard process?
θ/τ above about 1: dead time dominates.