Cohen–Coon PI and PID Tuning

PI and PID settings by the Cohen–Coon open-loop rules from the process gain, time constant and dead time of a step test (first order plus dead time).

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Gain 2, 60 s, 10 sGain 0.5, 120 s, 60 sGain 3, 20 s, 2 s

Results

Cohen–Coon settings are aggressive (quarter-decay); many engineers start with half the gain.

PI controller gain3.0278
PI integral time5.5091s
PID controller gain4.5278
PID integral time4.7246s
PID derivative time0.71429s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Gain 2, 60 s, 10 s. The inputs, in the units selected above:

InputValue
Process gain (change in output / change in controller output)2.0000 -
Process time constant60.000 s
Dead time10.000 s

Applying the formula below gives:

ResultValue
PI controller gain2.7417
PI integral time24.730 s
PID controller gain4.1250
PID integral time23.023 s
PID derivative time3.5294 s

Open this example in the calculator and change any input.

Formula

\(\text{PI: } K_c = \frac{\tau}{K_p\theta}\left(0.9 + \frac{\theta}{12\tau}\right), \quad T_i = \theta\, \frac{30 + 3\theta/\tau}{9 + 20\theta/\tau}\)

\(\text{PID: } K_c = \frac{\tau}{K_p\theta}\left(\frac43 + \frac{\theta}{4\tau}\right), \quad T_i = \theta\, \frac{32 + 6\theta/\tau}{13 + 8\theta/\tau}, \quad T_d = \frac{4\theta}{11 + 2\theta/\tau}\)

Variables

Symbol Meaning SI unit
\(K_p\) Process gain (change in output / change in controller output) -
\(\tau\) Process time constant s
\(\theta\) Dead time s
\(K_{c,PI}\) PI controller gain -
\(T_{i,PI}\) PI integral time s
\(K_{c,PID}\) PID controller gain -
\(T_{i,PID}\) PID integral time s
\(T_{d,PID}\) PID derivative time s

Method and standards

Cohen–Coon process reaction curve rules.

Where it is used

  • Tuning from a bump test.
  • Control engineering examinations.

Common mistakes

  • Using it on integrating processes.
  • No detuning for noisy loops.

Assumptions and limits

  • Self-regulating first-order plus dead-time process; θ/τ outside about 0.1 to 1 is flagged.
  • PID settings for the ideal (parallel, ISA standard) form K_c[1 + 1/(T_i s) + T_d s]. A series (interacting) controller needs its settings converted.

References

  • G.H. Cohen and G.A. Coon
  • Theoretical consideration of retarded control
  • Trans. ASME 75 (1953) 827

Questions and answers

Gain 2, τ 60 s, θ 10 s: what PI settings?

K_c = 2.74, T_i = 24.7 s.

Why are they aggressive?

They aim at quarter-amplitude decay, which overshoots.

When do they suit?

Processes with dead time comparable to the time constant.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.