Worked example
Example: Gain 2, 60 s, 10 s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Process gain (change in output / change in controller output) | 2.0000 - |
| Process time constant | 60.000 s |
| Dead time | 10.000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| PI controller gain | 2.7417 |
| PI integral time | 24.730 s |
| PID controller gain | 4.1250 |
| PID integral time | 23.023 s |
| PID derivative time | 3.5294 s |
Open this example in the calculator and change any input.
Formula
\(\text{PI: } K_c = \frac{\tau}{K_p\theta}\left(0.9 + \frac{\theta}{12\tau}\right), \quad T_i = \theta\, \frac{30 + 3\theta/\tau}{9 + 20\theta/\tau}\)
\(\text{PID: } K_c = \frac{\tau}{K_p\theta}\left(\frac43 + \frac{\theta}{4\tau}\right), \quad T_i = \theta\, \frac{32 + 6\theta/\tau}{13 + 8\theta/\tau}, \quad T_d = \frac{4\theta}{11 + 2\theta/\tau}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(K_p\) | Process gain (change in output / change in controller output) | - |
| \(\tau\) | Process time constant | s |
| \(\theta\) | Dead time | s |
| \(K_{c,PI}\) | PI controller gain | - |
| \(T_{i,PI}\) | PI integral time | s |
| \(K_{c,PID}\) | PID controller gain | - |
| \(T_{i,PID}\) | PID integral time | s |
| \(T_{d,PID}\) | PID derivative time | s |
Method and standards
Cohen–Coon process reaction curve rules.
Where it is used
- Tuning from a bump test.
- Control engineering examinations.
Common mistakes
- Using it on integrating processes.
- No detuning for noisy loops.
Assumptions and limits
- Self-regulating first-order plus dead-time process; θ/τ outside about 0.1 to 1 is flagged.
- PID settings for the ideal (parallel, ISA standard) form K_c[1 + 1/(T_i s) + T_d s]. A series (interacting) controller needs its settings converted.
References
- G.H. Cohen and G.A. Coon
- Theoretical consideration of retarded control
- Trans. ASME 75 (1953) 827
Questions and answers
Gain 2, τ 60 s, θ 10 s: what PI settings?
K_c = 2.74, T_i = 24.7 s.
Why are they aggressive?
They aim at quarter-amplitude decay, which overshoots.
When do they suit?
Processes with dead time comparable to the time constant.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.