Worked example
Example: Illustrative 15 % across 3.2 m to 2.5 m exit. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Measured opacity | 15.000 % |
| Measurement path length | 3.2000 m |
| Stack exit path length | 2.5000 m |
| Specific extinction coefficient | 2.5000 m²/g |
Applying the formula below gives:
| Result | Value |
|---|---|
| Optical density at measurement | 0.070581 |
| Opacity at stack exit | 11.924 % |
| Extinction coefficient | 0.050787 1/m |
| Estimated dust concentration | 20.315 mg/m³ |
Open this example in the calculator and change any input.
Formula
\(D = -\log_{10}(1 - Op), \quad D_2 = D_1\frac{L_2}{L_1}, \quad b = \frac{2.303D_1}{L_1}, \quad c = \frac{b}{K_e}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Op_1\) | Measured opacity | - |
| \(L_1\) | Measurement path length | m |
| \(L_2\) | Stack exit path length | m |
| \(K_e\) | Specific extinction coefficient | m²/kg |
| \(D_1\) | Optical density at measurement | - |
| \(Op_2\) | Opacity at stack exit | - |
| \(b\) | Extinction coefficient | 1/m |
| \(c\) | Estimated dust concentration | kg/m³ |
Method and standards
Opacity.
Where it is used
- Continuous opacity monitoring at boiler stacks.
- Checking ESP and bag filter performance.
Common mistakes
- Comparing opacities measured over different paths.
- Using a K_e from another plant.
Assumptions and limits
- Uniform particle cloud across the path; single scattering.
References
- Bouguer attenuation for transmissometers
Questions and answers
Why correct opacity to the stack exit?
Opacity depends on how far light travels through the smoke; limits refer to the plume diameter at the exit.
Can an opacity monitor measure dust in mg/m³?
Only with a site calibration against gravimetric samples; the relation changes with particle size and fuel.
What do the defaults represent?
An illustrative 15 % opacity measured across a 3.2 m duct, corrected to a 2.5 m exit, with K_e = 2.5 m²/g.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Lipták, Instrument Engineers' Handbook, Vol. 1: Process Measurement and Analysis, 4th ed. (CRC, 2003)