Vapour Compression Refrigeration Cycle from Enthalpies

Refrigerant flow, compressor power, condenser heat, refrigerating effect, COP and kW per ton of a vapour compression cycle from the enthalpies read off the p–h chart.

Food, dairy and textileAir conditioning and chillersRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: 100 kW chiller: 400 / 430 / 250 kJ/kg50 TR: 405 / 440 / 260 kJ/kgCold store 20 kW: 390 / 435 / 240 kJ/kg

Results

Read all three enthalpies from the same chart or table: refrigerant tables use different reference states, so mixing sources gives nonsense.

Refrigerating effect h₁ − h₄145.00kJ/kg
Compressor work h₂ − h₁35.000kJ/kg
Refrigerant flow4,365.7kg/h
Compressor power (to the refrigerant)42.445kW
Heat rejected in the condenser218.29kW
Coefficient of performance4.1429
Power per ton of refrigeration0.84890

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 100 kW chiller: 400 / 430 / 250 kJ/kg. The inputs, in the units selected above:

InputValue
Refrigerating capacity100.00 kW
Enthalpy at compressor suction400.00 kJ/kg
Enthalpy at compressor discharge430.00 kJ/kg
Enthalpy leaving the condenser (= h₄ after the expansion valve)250.00 kJ/kg

Applying the formula below gives:

ResultValue
Refrigerating effect h₁ − h₄150.00 kJ/kg
Compressor work h₂ − h₁30.000 kJ/kg
Refrigerant flow2,400.0 kg/h
Compressor power (to the refrigerant)20.000 kW
Heat rejected in the condenser120.00 kW
Coefficient of performance5.0000
Power per ton of refrigeration0.70337

Open this example in the calculator and change any input.

Formula

\(q_e = h_1 - h_4, \quad w = h_2 - h_1, \quad \dot m = \frac{\dot Q_e}{q_e}\)

\(COP = \frac{h_1 - h_4}{h_2 - h_1}, \quad \dot Q_c = \dot m (h_2 - h_3)\)

Variables

Symbol Meaning SI unit
\(\dot Q_e\) Refrigerating capacity W
\(h_1\) Enthalpy at compressor suction J/kg
\(h_2\) Enthalpy at compressor discharge J/kg
\(h_3\) Enthalpy leaving the condenser (= h₄ after the expansion valve) J/kg
\(q_e\) Refrigerating effect h₁ − h₄ J/kg
\(w\) Compressor work h₂ − h₁ J/kg
\(\dot m\) Refrigerant flow kg/s
\(P\) Compressor power (to the refrigerant) W
\(\dot Q_c\) Heat rejected in the condenser W
\(COP\) Coefficient of performance -
\(kW/TR\) Power per ton of refrigeration -

Method and standards

Steady energy balance on each component; the expansion valve is isenthalpic (h₄ = h₃).

Where it is used

  • Chiller and cold store checks.
  • Refrigeration examinations.
  • Comparing refrigerants.

Common mistakes

  • Using h₃ ≠ h₄.
  • Mixing enthalpy references.
  • Power to refrigerant taken as motor power.

Assumptions and limits

  • Ideal compressor power to the refrigerant; no line losses.

References

  • Vapour compression cycle energy balance (ASHRAE Handbook—Fundamentals, ch. 2)

Questions and answers

What COP for 400, 430 and 250 kJ/kg?

Refrigerating effect 150 kJ/kg, work 30 kJ/kg: COP 5.0, which is 0.70 kW/TR.

What flow for 100 kW?

0.667 kg/s of refrigerant, needing 20 kW of compression and rejecting 120 kW.

Why must the enthalpies come from one chart?

Different tables use different reference states.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.