FireCADCalc

Two-Stage Refrigeration: Optimum Intermediate Pressure

Intermediate (interstage) pressure for a two-stage or compound refrigeration system by the geometric mean rule, with overall and per-stage pressure ratios.

Process steam and utilitiesDistillery and ethanolChemical and fertiliserFood, dairy and textile

Inputs

Examples: Ammonia −35/40 °CR404A freezer 1.4/18 bar

Results

The geometric mean gives equal stage ratios and near-minimum work; the true optimum is a little higher for ammonia with an intercooler. Pressure ratios above about 8–10 in one stage call for two stages.

Intermediate pressure5.0200bar
Overall pressure ratio12.857
Pressure ratio per stage3.5857

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Ammonia −35/40 °C. The inputs, in the units selected above:

InputValue
Evaporating pressure (absolute)0.93000 bar
Condensing pressure (absolute)15.500 bar

Applying the formula below gives:

ResultValue
Intermediate pressure3.7967 bar
Overall pressure ratio16.667
Pressure ratio per stage4.0825

Open this example in the calculator and change any input.

Formula

\(p_i = \sqrt{p_ep_c}, \quad r_s = \sqrt{\frac{p_c}{p_e}}\)

Variables

Symbol Meaning SI unit
\(p_e\) Evaporating pressure (absolute) Pa
\(p_c\) Condensing pressure (absolute) Pa
\(p_i\) Intermediate pressure Pa
\(p_c/p_e\) Overall pressure ratio -
\(r_s\) Pressure ratio per stage -

Method and standards

Equal pressure ratio.

Where it is used

  • Freezing and cold-store plants.
  • Choosing compound versus single-stage compressors.

Common mistakes

  • Using gauge pressures.
  • Ignoring intercooler pressure drop.

Assumptions and limits

  • Ideal gas; equal stage efficiency.

References

  • Geometric-mean interstage pressure p_i = √(p_ep_c) (ASHRAE Handbook—Refrigeration (2018), ch. 2, multistage systems)

Questions and answers

When are two stages needed?

When the overall pressure ratio is large (low-temperature freezing with ammonia): one stage would have poor volumetric efficiency and very hot discharge.

Is the geometric mean exact?

It is the ideal-gas optimum for equal stage efficiency; real systems with intercoolers shift it slightly.

What do the defaults represent?

An ammonia system evaporating near −35 °C and condensing near 40 °C.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.