Worked example
Example: 400 → 430 kJ/kg, η 0.7, 0.5 kg/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Suction enthalpy | 400.00 kJ/kg |
| Isentropic discharge enthalpy | 430.00 kJ/kg |
| Isentropic efficiency | 70.000 % |
| Refrigerant mass flow | 1,800.0 kg/h |
| Motor and drive efficiency | 92.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Actual discharge enthalpy | 442.86 kJ/kg |
| Isentropic power | 15.000 kW |
| Shaft power | 21.429 kW |
| Electrical input | 23.292 kW |
Open this example in the calculator and change any input.
Formula
\(h_2 = h_1 + \frac{h_{2s} - h_1}{\eta_s}, \quad W = \frac{\dot m(h_{2s} - h_1)}{\eta_s}, \quad W_e = \frac{W}{\eta_m}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(h_1\) | Suction enthalpy | J/kg |
| \(h_{2s}\) | Isentropic discharge enthalpy | J/kg |
| \(\eta_s\) | Isentropic efficiency | - |
| \(\dot m\) | Refrigerant mass flow | kg/s |
| \(\eta_m\) | Motor and drive efficiency | - |
| \(h_2\) | Actual discharge enthalpy | J/kg |
| \(W_s\) | Isentropic power | W |
| \(W\) | Shaft power | W |
| \(W_e\) | Electrical input | W |
Method and standards
Compression process.
Where it is used
- Compressor selection checks.
- Discharge temperature limits.
Common mistakes
- Using saturated instead of superheated suction enthalpy.
- Mixing kJ/kg and kcal/kg.
Assumptions and limits
- Steady adiabatic compression.
References
- ASHRAE Handbook—Refrigeration (2018)
- ch. 2 (compression process: h₂ = h₁ + (h₂s − h₁)/η_s)
Questions and answers
Where do the enthalpies come from?
From the refrigerant's p–h chart or tables: suction state, then along constant entropy to discharge pressure.
Why is actual discharge hotter?
Losses add heat to the gas; lower isentropic efficiency gives a hotter discharge and more power.
What do the defaults represent?
A mid-size compressor with enthalpies typical of an HFC at air-conditioning conditions.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.