Worked example
Example: 2 t frozen to −18 °C in 24 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Product mass per batch | 2,000.0 kg |
| Entering temperature | 30.000 °C |
| Freezing point | -2.0000 °C |
| Final temperature | -18.000 °C |
| Specific heat above freezing | 3.6000 kJ/(kg·K) |
| Latent heat of freezing of the product | 250.00 kJ/kg |
| Specific heat below freezing | 1.9000 kJ/(kg·K) |
| Pull-down time | 24.000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Cooling to the freezing point | 64.000 kWh |
| Freezing | 138.89 kWh |
| Sub-cooling | 16.889 kWh |
| Total per batch | 219.78 kWh |
| Average load over the pull-down | 9.1574 kW |
Open this example in the calculator and change any input.
Formula
\(Q = m\left[c_1(T_1 - T_f) + L_f + c_2(T_f - T_2)\right], \quad \dot Q = \frac{Q}{t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m\) | Product mass per batch | kg |
| \(T_1\) | Entering temperature | K |
| \(T_f\) | Freezing point | K |
| \(T_2\) | Final temperature | K |
| \(c_1\) | Specific heat above freezing | J/(kg·K) |
| \(L_f\) | Latent heat of freezing of the product | J/kg |
| \(c_2\) | Specific heat below freezing | J/(kg·K) |
| \(t\) | Pull-down time | s |
| \(Q_1\) | Cooling to the freezing point | J |
| \(Q_2\) | Freezing | J |
| \(Q_3\) | Sub-cooling | J |
| \(Q\) | Total per batch | J |
| \(\dot Q\) | Average load over the pull-down | W |
Method and standards
Sensible and latent heat.
Where it is used
- Cold store and freezer sizing.
- Ice cream, fish, meat and vegetable plants.
Common mistakes
- Product properties at the wrong water content.
- No pull-down margin.
Assumptions and limits
- Freezing at one temperature, with all the latent heat released there and the product fully frozen; real foods freeze over a range and keep some unfrozen water, so the latent part is slightly overstated at moderate final temperatures.
References
- Sensible and latent heat Q = m[c₁(T₁ − T_f) + L_f + c₂(T_f − T₂)] (ASHRAE Handbook—Refrigeration, load calculations)
Questions and answers
2 t from 30 °C frozen to −18 °C in 24 h?
About 64 kWh to the freezing point, 139 kWh to freeze and 17 kWh to sub-cool: about 9.2 kW average.
Where do the properties come from?
Product data tables; they depend on water content.
Product already frozen?
Enter an entering temperature below the freezing point: only sub-cooling is counted.