FireCADCalc

Condenser Heat Rejection and Heat Rejection Factor

Heat a refrigeration condenser must reject from the evaporator load and compressor power (open or hermetic), the heat rejection factor and the condenser water flow.

Process steam and utilitiesDistillery and ethanolChemical and fertiliserFood, dairy and textile

Inputs

Examples: 350 kW open drive, COP 4.5Hermetic 100 kW, COP 3.2

Results

In hermetic compressors the motor losses are absorbed by the refrigerant and also go to the condenser. Oil coolers and desuperheaters reduce condenser duty when heat is taken separately.

Compressor shaft power31.250kW
Condenser heat rejection134.72kW
Heat rejection factor Q_c/Q_e1.3472
Condenser water flow21.066t/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 350 kW open drive, COP 4.5. The inputs, in the units selected above:

InputValue
Refrigeration capacity350.00 kW
COP on compressor shaft power4.5000 -
Compressor typeOpen drive (motor outside)
Motor efficiency92.000 %
Condenser water temperature rise5.0000 K

Applying the formula below gives:

ResultValue
Compressor shaft power77.778 kW
Condenser heat rejection427.78 kW
Heat rejection factor Q_c/Q_e1.2222
Condenser water flow73.579 t/h

Open this example in the calculator and change any input.

Formula

\(Q_c = Q_e + W\ \text{(open)}, \quad Q_c = Q_e + \frac{W}{\eta_m}\ \text{(hermetic)}, \quad HRF = \frac{Q_c}{Q_e}, \quad \dot m_w = \frac{Q_c}{c_p \Delta T_w},\ c_p = 4186\ \mathrm{J/(kg\,K)}\)

Variables

Symbol Meaning SI unit
\(Q_e\) Refrigeration capacity W
\(COP\) COP on compressor shaft power -
\(\text{compressor}\) Compressor type -
\(\eta_m\) Motor efficiency -
\(\Delta T_w\) Condenser water temperature rise K
\(W\) Compressor shaft power W
\(Q_c\) Condenser heat rejection W
\(HRF\) Heat rejection factor Q_c/Q_e -
\(\dot m_w\) Condenser water flow kg/s

Method and standards

Energy balance.

Where it is used

  • Cooling tower and condenser sizing.
  • Heat recovery from condensers.

Common mistakes

  • Sizing the tower on refrigeration capacity alone.
  • Ignoring motor heat in hermetic units.

Assumptions and limits

  • Steady state; heat lost from the compressor shell and discharge line is ignored (all compressor work goes to the condenser).
  • Condenser water c_p 4186 J/(kg·K).

References

  • ASHRAE Handbook—Refrigeration (2018)
  • ch. 39 (condensers: Q_c = Q_e + W)

Questions and answers

Why is the condenser bigger than the evaporator?

It rejects the evaporator heat plus the compressor work, typically 1.2–1.3 times the capacity.

Why do hermetic compressors add more?

Motor losses heat the suction gas, so they too end up in the condenser.

What do the defaults represent?

A 350 kW (about 100 TR) water-cooled chiller with a hermetic-or-open choice and a 5 K water rise.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.