FireCADCalc

Cold Room Refrigeration Load

Daily heat load and refrigeration capacity of a cold room or freezer from wall transmission, air changes, product cooling and freezing, and internal loads.

Chemical and fertiliserFood, dairy and textileAir conditioning and chillersRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: Chiller room 6 x 5 x 3 m at 2 °C, 2 t/day loaded at 30 °CFreezer 8 x 6 x 4 m at −20 °C, 3 t/day loaded at 5 °CVegetable store 4 x 3 x 3 m at 5 °C, 1 t/day at 28 °C

Room

Outside

Product

Results

Product cooled to room temperature within the day; respiration heat of fruit and vegetables, packaging and solar gain on the roof are not included. Saturation over ice below 0 °C (IAPWS R14-08).

Transmission through the envelope per day24.948kWh
Air changes per day24.986kWh
Product cooling and freezing per day56.000kWh
Internal loads per day36.000kWh
Total heat per day141.93kWh
Refrigeration capacity needed8.6738kW
Refrigeration capacity needed, in tons of refrigeration (same as Q)2.4663TR

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Chiller room 6 x 5 x 3 m at 2 °C, 2 t/day loaded at 30 °C. The inputs, in the units selected above:

InputValue
Inside length6.0000 m
Inside width5.0000 m
Inside height3.0000 m
U-value of walls, roof and floor0.25000 W/(m²·K)
Room temperature2.0000 °C
Room relative humidity90.000 %
Outside air temperature35.000 °C
Outside relative humidity60.000 %
Air changes (door openings)10.000 1/d
Product loaded per day2,000.0 kg
Product temperature when loaded30.000 °C
Specific heat of the product above freezing3.6000 kJ/(kg·K)
Freezing point of the product-2.0000 °C
Latent heat of freezing of the product250.00 kJ/kg
Specific heat of the product below freezing1.8000 kJ/(kg·K)
People, lights, fans and defrost (average)1,500.0 W
Safety margin10.000 %
Compressor running hours per day18.000 h

Applying the formula below gives:

ResultValue
Transmission through the envelope per day24.948 kWh
Air changes per day24.986 kWh
Product cooling and freezing per day56.000 kWh
Internal loads per day36.000 kWh
Total heat per day141.93 kWh
Refrigeration capacity needed8.6738 kW
Refrigeration capacity needed, in tons of refrigeration (same as Q)2.4663 TR

Open this example in the calculator and change any input.

Formula

\(E_t = U \cdot 2(LW + LH + WH)(T_o - T_r)\, t_d\)

\(E_a = L W H\, n\, t_d\, \rho_{da} (h_o - h_r)\)

\(E_p = m_p c_1 (T_{in} - T_r)\ \text{or}\ m_p [c_1 (T_{in} - T_f) + L_f + c_2 (T_f - T_r)]\)

\(Q = \frac{(E_t + E_a + E_p + E_i)(1 + k_s)}{t_r}\)

Variables

Symbol Meaning SI unit
\(L\) Inside length m
\(W\) Inside width m
\(H\) Inside height m
\(U\) U-value of walls, roof and floor W/(m²·K)
\(T_r\) Room temperature K
\(\varphi_r\) Room relative humidity -
\(T_o\) Outside air temperature K
\(\varphi_o\) Outside relative humidity -
\(n\) Air changes (door openings) 1/s
\(m_p\) Product loaded per day kg
\(T_{in}\) Product temperature when loaded K
\(c_1\) Specific heat of the product above freezing J/(kg·K)
\(T_f\) Freezing point of the product K
\(L_f\) Latent heat of freezing of the product J/kg
\(c_2\) Specific heat of the product below freezing J/(kg·K)
\(Q_{int}\) People, lights, fans and defrost (average) W
\(k_s\) Safety margin -
\(t_r\) Compressor running hours per day s
\(E_t\) Transmission through the envelope per day J
\(E_a\) Air changes per day J
\(E_p\) Product cooling and freezing per day J
\(E_i\) Internal loads per day J
\(E\) Total heat per day J
\(Q\) Refrigeration capacity needed W
\(Q_{TR}\) Refrigeration capacity needed, in tons of refrigeration (same as Q) W
\(t_d\) Seconds in a day s
\(\rho_{da}\) Dry air density in the room kg/m³
\(h_o, h_r\) Moist-air enthalpy outside and in the room J/kg

Method and standards

The heat entering in a day by transmission, air exchange and product, plus internal gains, is removed in the compressor running hours. Moist-air enthalpy follows ASHRAE Fundamentals ch. 1, with saturation over ice below 0 °C.

Where it is used

  • Sizing condensing units for cold rooms and freezers.
  • Checking an existing plant after more product or more door openings.
  • Comparing panel thicknesses.

Common mistakes

  • Forgetting the floor in the envelope area.
  • Ignoring defrost and evaporator fan heat.
  • Taking the product to room temperature in less than the time allowed.

Assumptions and limits

  • Daily average; pull-down within the day.
  • Respiration heat not included.
  • Sea-level pressure (101 325 Pa); no altitude input. The air-change load uses the room's dry-air density and the outside enthalpy; the latent heat of frost formed on the coil is not included.

References

  • ASHRAE Handbook—Refrigeration
  • ch. 24 Refrigerated-facility loads (method)
  • IAPWS R14-08 saturation over ice

Questions and answers

What capacity does a 6 × 5 × 3 m chiller room need?

At 2 °C with 2 t/day of produce at 30 °C, about 511 MJ a day; with 10 % margin over 18 running hours, 8.7 kW (2.5 TR).

Why so much for air changes?

Each door opening lets warm moist air in; cooling and drying it can match the wall load in a busy room.

How does a freezer differ?

Product is cooled to its freezing point, frozen (latent heat) and cooled further: 3 t/day at 5 °C into −20 °C needs 849 MJ for product alone.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.