Worked example
Example: 5 t product, 20 kW, UA 200 W/K, 30 → 2 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Product mass (plus equivalent of structure) | 5,000.0 kg |
| Product specific heat (above freezing) | 3.6000 kJ/(kg·K) |
| Refrigeration capacity | 20.000 kW |
| Room heat gain coefficient | 0.20000 kW/K |
| Ambient temperature | 35.000 °C |
| Start temperature | 30.000 °C |
| Target temperature | 2.0000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Lowest temperature the plant can hold | -65.000 °C |
| Time constant mc/UA | 25.000 h |
| Pull-down time | 8.7296 h |
Open this example in the calculator and change any input.
Formula
\(t = \frac{mc}{UA}\ln\frac{Q_r - UA(t_a - t_0)}{Q_r - UA(t_a - t_1)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m_p\) | Product mass (plus equivalent of structure) | kg |
| \(c_p\) | Product specific heat (above freezing) | J/(kg·K) |
| \(Q_r\) | Refrigeration capacity | W |
| \(UA\) | Room heat gain coefficient | W/K |
| \(t_a\) | Ambient temperature | K |
| \(t_0\) | Start temperature | K |
| \(t_1\) | Target temperature | K |
| \(t_{min}\) | Lowest temperature the plant can hold | K |
| \(\tau\) | Time constant mc/UA | s |
| \(t\) | Pull-down time | s |
Method and standards
Lumped transient balance.
Where it is used
- Cold store commissioning.
- Checking plant size for loading cycles.
Common mistakes
- Ignoring structure and air mass.
- Using rated capacity at the start temperature.
Assumptions and limits
- Uniform product temperature.
- Constant refrigeration capacity: real capacity falls as the room cools, so the actual pull-down is slower; enter the capacity at the target temperature for a conservative time.
References
- Lumped energy balance mc dT/dt = −Q_r + UA(T_a − T) (heat transfer definitions)
Questions and answers
Why does pull-down slow near the target?
Wall heat gain grows as the room gets colder, leaving less capacity to cool the product.
What limits the lowest temperature?
When wall gain equals plant capacity: t_min = t_a − Q_r/UA.
What do the defaults represent?
Five tonnes of fruit-like product cooled from 30 °C to 2 °C in a room with modest wall gain.