Electric Duct Heater: Power and Current

Power of an electric duct heater to warm an air flow from one temperature to another (moist-air enthalpy), with the current for a single- or three-phase supply.

Inputs

Examples: 3000 m³/h, 10 to 30 °C, 415 VReheat 800 m³/h, 13 to 20 °C, 230 V

Results

Heater power1.9343kW
Line current8.4101A
Outlet relative humidity57.637%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3000 m³/h, 10 to 30 °C, 415 V. The inputs, in the units selected above:

InputValue
Air flow (at the inlet)3,000.0 m³/h
Inlet air temperature10.000 °C
Inlet relative humidity50.000 %
Outlet air temperature30.000 °C
Supply voltage (line)415.00 V
SupplyThree-phase
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Heater power20.922 kW
Line current29.106 A
Outlet relative humidity14.460 %

Open this example in the calculator and change any input.

Formula

\(P = \dot m_{da}\left[h(T_2, W) - h(T_1, W)\right], \quad I = \frac{P}{\sqrt{3}U}\ \text{(three-phase)},\quad I = \frac{P}{U}\ \text{(single-phase)}\)

Variables

Symbol Meaning SI unit
\(\dot V\) Air flow (at the inlet) m³/s
\(T_1\) Inlet air temperature K
\(\varphi_1\) Inlet relative humidity -
\(T_2\) Outlet air temperature K
\(U\) Supply voltage (line) V
\(\text{phases}\) Supply -
\(p\) Barometric pressure (absolute) Pa
\(P\) Heater power W
\(I\) Line current A
\(\varphi_2\) Outlet relative humidity -

Method and standards

Energy balance.

Where it is used

  • Reheat and frost heaters.
  • Panel and control room heaters.

Common mistakes

  • Volume at the outlet.
  • Forgetting the √3.

Assumptions and limits

  • Resistive heater, unity power factor.

References

  • Moist-air energy balance (ASHRAE Handbook—Fundamentals ch. 1); P = √3 U I for three-phase

Questions and answers

3000 m³/h from 10 to 30 °C?

About 20.9 kW, 29 A on 415 V three-phase.

Why does RH fall?

Heating adds no moisture, so relative humidity drops.

Safety?

Interlock with air flow and fit a high-limit cut-out.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.