Worked example
Example: Fine filter at lower flow. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pressure drop at the reference flow | 12.237 mmWC |
| Reference flow | 3,400.0 m³/h |
| New flow | 3,000.0 m³/h |
| Flow exponent | 1.0000 - |
| Final (change) pressure drop | 25.493 mmWC |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pressure drop at the new flow | 10.797 mmWC |
| Share of the final drop | 42.353 % |
Open this example in the calculator and change any input.
Formula
\(\Delta p_2 = \Delta p_1\left(\frac{\dot V_2}{\dot V_1}\right)^n\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\Delta p_1\) | Pressure drop at the reference flow | Pa |
| \(\dot V_1\) | Reference flow | m³/s |
| \(\dot V_2\) | New flow | m³/s |
| \(n\) | Flow exponent | - |
| \(\Delta p_f\) | Final (change) pressure drop | Pa |
| \(\Delta p_2\) | Pressure drop at the new flow | Pa |
| \(\Delta p_2/\Delta p_f\) | Share of the final drop | - |
Method and standards
Power law.
Where it is used
- AHU filter monitoring.
- Fan selection with dirty filters.
Common mistakes
- Squared law for fine filters.
- Comparing clean and dirty drops.
Assumptions and limits
- Same filter loading. A drop above the final (change) value is flagged.
References
- Power law Δp ∝ V̇ⁿ (n ≈ 1 for laminar flow through fibrous media)
Questions and answers
120 Pa at 3400 m³/h, run at 3000 m³/h?
About 106 Pa with n = 1.
Why n = 1?
Flow through fine fibres is laminar, so drop is proportional to velocity.
When to change filters?
At the final drop the maker or your fan selection allows.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.