Worked example
Example: Rectangular 800 × 500, 50 m, 25 mm insulation. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Duct shape | Rectangular |
| Diameter (round) | 400.00 mm |
| Width (rectangular) | 800.00 mm |
| Height (rectangular) | 500.00 mm |
| Length | 50.000 m |
| Sheet thickness | 0.80000 mm |
| Sheet density | 7,850.0 kg/m³ |
| Allowance for seams, joints and stiffeners | 15.000 % |
| Insulation thickness (0 if none) | 25.000 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Sheet area (with allowance) | 149.50 m² |
| Sheet weight | 938.86 kg |
| Insulation outer area | 140.00 m² |
| Insulation volume | 3.3750 m³ |
Open this example in the calculator and change any input.
Formula
\(A_s = P L (1 + k_s), \quad m = A_s t \rho\) \(A_i = P_i L, \quad V_i = (A_{out} - A_{in}) L, \quad P_i = \pi(D + 2t_i)\ \text{or}\ 2(W + H + 4t_i), \quad A_{out} = \frac{\pi (D + 2t_i)^2}{4}\ \text{or}\ (W + 2t_i)(H + 2t_i)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{shape}\) | Duct shape | - |
| \(D\) | Diameter (round) | m |
| \(W\) | Width (rectangular) | m |
| \(H\) | Height (rectangular) | m |
| \(L\) | Length | m |
| \(t\) | Sheet thickness | m |
| \(\rho\) | Sheet density | kg/m³ |
| \(k_s\) | Allowance for seams, joints and stiffeners | - |
| \(t_i\) | Insulation thickness (0 if none) | m |
| \(A_s\) | Sheet area (with allowance) | m² |
| \(m\) | Sheet weight | kg |
| \(A_i\) | Insulation outer area | m² |
| \(V_i\) | Insulation volume | m³ |
Method and standards
Geometry.
Where it is used
- Ductwork estimates and bills of quantities.
- Insulation orders.
Common mistakes
- Ignoring seams and stiffeners.
- Outer perimeter for sheet area.
Assumptions and limits
- Straight duct.
- Rectangular insulation is taken with square outer corners, slightly overstating its area and volume.
References
- Perimeter × length with allowance (estimating practice)
Questions and answers
50 m of 800 × 500 duct in 0.8 mm GI with 15 % allowance?
About 150 m² of sheet, roughly 940 kg.
Which thickness?
Your duct standard sets it by size and pressure class.
Fittings?
Measure them along their centre line or add a share.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.