FireCADCalc

Duct Leakage: Scaling a Test Result to Operating Pressure

Duct leakage at operating pressure from a leakage test at another pressure by the power law, as a share of system air flow.

Inputs

Examples: Test at 500 Pa, run at 300 PaOrifice-like leaks

0.5 for sharp orifices, 1 for laminar cracks; 0.65 is the usual assumption for ducts.

Results

Leakage at operating pressure35.873L/s
Share of system air flow1.4349%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Test at 500 Pa, run at 300 Pa. The inputs, in the units selected above:

InputValue
Leakage measured at the test pressure50.000 L/s
Test pressure50.986 mmWC
Average operating pressure30.591 mmWC
Flow exponent0.65000 -
System air flow9,000.0 m³/h

Applying the formula below gives:

ResultValue
Leakage at operating pressure35.873 L/s
Share of system air flow1.4349 %

Open this example in the calculator and change any input.

Formula

\(\dot V_2 = \dot V_1\left(\frac{\Delta p_2}{\Delta p_1}\right)^n, \quad x = \frac{\dot V_2}{\dot V_s}\)

Variables

Symbol Meaning SI unit
\(\dot V_1\) Leakage measured at the test pressure m³/s
\(\Delta p_1\) Test pressure Pa
\(\Delta p_2\) Average operating pressure Pa
\(n\) Flow exponent -
\(\dot V_s\) System air flow m³/s
\(\dot V_2\) Leakage at operating pressure m³/s
\(x\) Share of system air flow -

Method and standards

Power law.

Where it is used

  • Duct testing and commissioning.
  • Fan sizing allowances.

Common mistakes

  • Linear scaling with pressure.
  • Peak instead of average duct pressure.

Assumptions and limits

  • Same leak paths at both pressures.
  • The share is not shown when the system air flow is zero.

References

  • Power-law leakage Q = C Δpⁿ with n = 0.65 for ducts (ASHRAE Handbook—Fundamentals (2017), ch. 21, duct leakage)

Questions and answers

50 L/s at 500 Pa test, 300 Pa operating?

About 36 L/s, 1.4 % of 2.5 m³/s.

Why 0.65?

Real leaks lie between orifice and crack flow.

Acceptable leakage?

Your specification's class sets it.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.