Duct Sizing by the Equal-Friction Method

Round duct diameter for an air flow at a chosen friction rate (Colebrook friction factor), the velocity, and the equivalent rectangular duct for an aspect ratio.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 2 m³/s at 1 Pa/m, galvanisedBranch 0.4 m³/s at 0.8 Pa/m, 3:1

Results

Darcy–Weisbach with the Colebrook friction factor; rectangular size from Huebscher's equivalent diameter D_e = 1.30(ab)^0.625/(a + b)^0.25. Typical friction rates: 0.8–1.0 Pa/m for low-pressure supply ducts. Round the result up to a standard size.

Round duct diameter327.14mm
Velocity4.7589m/s
Reynolds number103,214
Rectangular duct, long side537.31mm
Rectangular duct, short side179.10mm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 m³/s at 1 Pa/m, galvanised. The inputs, in the units selected above:

InputValue
Air flow7,200.0 m³/h
Friction rate1.0000 Pa/m
Duct roughness0.090000 mm
Air density1.2000 kg/m³
Air viscosity1.8100e-05 Pa·s
Rectangular aspect ratio2.0000 -

Applying the formula below gives:

ResultValue
Round duct diameter573.54 mm
Velocity7.7413 m/s
Reynolds number294,360
Rectangular duct, long side752.99 mm
Rectangular duct, short side376.49 mm

Open this example in the calculator and change any input.

Formula

\(\frac{\Delta p}{L} = \frac{f}{D}\frac{\rho v^2}{2}, \quad \frac{1}{\sqrt f} = -2\log_{10}\left(\frac{\varepsilon}{3.7D} + \frac{2.51}{Re\sqrt f}\right), \quad D_e = \frac{1.30(ab)^{0.625}}{(a + b)^{0.25}}\)

Variables

Symbol Meaning SI unit
\(\dot V\) Air flow m³/s
\(\Delta p/L\) Friction rate, in Pa/m (1 in WC per 100 ft = 8.17 Pa/m) -
\(\varepsilon\) Duct roughness m
\(\rho\) Air density kg/m³
\(\mu\) Air viscosity Pa·s
\(a/b\) Rectangular aspect ratio -
\(D\) Round duct diameter m
\(v\) Velocity m/s
\(Re\) Reynolds number -
\(a\) Rectangular duct, long side m
\(b\) Rectangular duct, short side m

Method and standards

Colebrook and Huebscher.

Where it is used

  • Supply and return duct layout.
  • Rectangular duct selection for ceiling space.

Common mistakes

  • Mixing Pa/m and Pa/100 ft.
  • Very flat rectangular ducts (aspect ratio above 4).

Assumptions and limits

  • Fully developed turbulent flow; standard air.
  • The friction rate is entered in Pa/m in every unit system; 1 in WC per 100 ft is 8.17 Pa/m.

References

  • ASHRAE Handbook—Fundamentals (2017)
  • ch. 21 (Darcy–Weisbach, Colebrook, Huebscher equivalent diameter, equal-friction method)

Questions and answers

What is the equal-friction method?

Every duct section is sized for the same pressure loss per metre, so the index run's loss is simply the friction rate times its length plus fittings.

Why not size by velocity?

Velocity sizing suits noise limits; equal friction keeps the pressure balance simpler on branched systems.

What do the defaults represent?

A main supply duct in galvanised steel at a friction rate of about 1 Pa/m.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.