Hot Water Cylinder Recovery Rate and Storage Volume

Recovery rate of a hot water heater, the hot-water equivalent of a peak draw at a lower use temperature, and the storage volume to meet the peak.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 12 kW, 60 °C store, 600 L at 40 °C in 1 hCanteen 50 kW gas at 90 %, 3,000 L at 45 °C over 2 h

Results

Water taken as 1,000 kg/m³ and 4.186 kJ/(kg·K). Store at 60 °C or above against Legionella. The usable fraction allows for mixing at the cold inlet.

Recovery rate (at storage temperature)774.01L/h
Hot fraction in mixed water60.000%
Peak draw as stored hot water1,800.0L
Storage volume required296.45L

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 12 kW, 60 °C store, 600 L at 40 °C in 1 h. The inputs, in the units selected above:

InputValue
Heater power12.000 kW
Heating efficiency100.00 %
Cold feed temperature10.000 °C
Storage temperature60.000 °C
Use (mixed) temperature40.000 °C
Peak draw at use temperature600.00 L
Peak period1.0000 h
Usable fraction of the store80.000 %

Applying the formula below gives:

ResultValue
Recovery rate (at storage temperature)206.40 L/h
Hot fraction in mixed water60.000 %
Peak draw as stored hot water360.00 L
Storage volume required192.00 L

Open this example in the calculator and change any input.

Formula

\(\dot V_{rec} = \frac{\eta P}{\rho c_p(t_s - t_c)}, \quad V_s = \frac{\max\left(V_{pk}\frac{t_u - t_c}{t_s - t_c} - \dot V_{rec}t_p,\ 0\right)}{f_u}\)

Variables

Symbol Meaning SI unit
\(P\) Heater power W
\(\eta\) Heating efficiency -
\(t_c\) Cold feed temperature K
\(t_s\) Storage temperature K
\(t_u\) Use (mixed) temperature K
\(V_{pk}\) Peak draw at use temperature m³
\(t_p\) Peak period s
\(f_u\) Usable fraction of the store -
\(\dot V_{rec}\) Recovery rate (at storage temperature) m³/s
\(f_h\) Hot fraction in mixed water -
\(V_h\) Peak draw as stored hot water m³
\(V_s\) Storage volume required m³

Method and standards

Store energy balance.

Where it is used

  • Hotel, hostel, hospital and canteen hot water.
  • Process wash water.

Common mistakes

  • Ignoring recovery during the peak.
  • Storing below 60 °C.

Assumptions and limits

  • Constant cold feed; perfect mixing at the outlet.

References

  • Energy balance of the store and mixing rule (CIBSE Guide G approach)

Questions and answers

What is recovery rate?

The volume of water the heater can raise from cold to storage temperature each hour.

Why convert to stored hot water?

People draw mixed water at 40 °C; less 60 °C water is needed because cold is blended in.

What do the defaults represent?

A 12 kW heater, a 60 °C store, 40 °C use and a one-hour peak draw.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.