Worked example
Example: 12 kW, 60 °C store, 600 L at 40 °C in 1 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heater power | 12.000 kW |
| Heating efficiency | 100.00 % |
| Cold feed temperature | 10.000 °C |
| Storage temperature | 60.000 °C |
| Use (mixed) temperature | 40.000 °C |
| Peak draw at use temperature | 600.00 L |
| Peak period | 1.0000 h |
| Usable fraction of the store | 80.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Recovery rate (at storage temperature) | 206.40 L/h |
| Hot fraction in mixed water | 60.000 % |
| Peak draw as stored hot water | 360.00 L |
| Storage volume required | 192.00 L |
Open this example in the calculator and change any input.
Formula
\(\dot V_{rec} = \frac{\eta P}{\rho c_p(t_s - t_c)}, \quad V_s = \frac{\max\left(V_{pk}\frac{t_u - t_c}{t_s - t_c} - \dot V_{rec}t_p,\ 0\right)}{f_u}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | Heater power | W |
| \(\eta\) | Heating efficiency | - |
| \(t_c\) | Cold feed temperature | K |
| \(t_s\) | Storage temperature | K |
| \(t_u\) | Use (mixed) temperature | K |
| \(V_{pk}\) | Peak draw at use temperature | m³ |
| \(t_p\) | Peak period | s |
| \(f_u\) | Usable fraction of the store | - |
| \(\dot V_{rec}\) | Recovery rate (at storage temperature) | m³/s |
| \(f_h\) | Hot fraction in mixed water | - |
| \(V_h\) | Peak draw as stored hot water | m³ |
| \(V_s\) | Storage volume required | m³ |
Method and standards
Store energy balance.
Where it is used
- Hotel, hostel, hospital and canteen hot water.
- Process wash water.
Common mistakes
- Ignoring recovery during the peak.
- Storing below 60 °C.
Assumptions and limits
- Constant cold feed; perfect mixing at the outlet.
References
- Energy balance of the store and mixing rule (CIBSE Guide G approach)
Questions and answers
What is recovery rate?
The volume of water the heater can raise from cold to storage temperature each hour.
Why convert to stored hot water?
People draw mixed water at 40 °C; less 60 °C water is needed because cold is blended in.
What do the defaults represent?
A 12 kW heater, a 60 °C store, 40 °C use and a one-hour peak draw.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.