Worked example
Example: Hot water 5 m³, 10 to 90 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| System water volume | 5.0000 m³ |
| Fill (lowest) temperature | 10.000 °C |
| Highest temperature | 90.000 °C |
| Pre-charge or fill pressure at the tank (absolute) | 2.5000 bar |
| Highest pressure at the tank (absolute, below the relief setting) | 5.0000 bar |
| Linear expansion coefficient of the piping | 11.700 µm/(m·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Specific volume at the fill temperature | 0.001000 m³/kg |
| Specific volume at the highest temperature | 0.001036 m³/kg |
| Net expansion volume | 164.06 L |
| Tank volume | 328.12 L |
Open this example in the calculator and change any input.
Formula
\(V_e = V_s\left[\left(\frac{v_2}{v_1} - 1\right) - 3\alpha\Delta T\right], \quad V_t = \frac{V_e}{1 - p_1/p_2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_s\) | System water volume | m³ |
| \(T_1\) | Fill (lowest) temperature | K |
| \(T_2\) | Highest temperature | K |
| \(p_1\) | Pre-charge or fill pressure at the tank (absolute) | Pa |
| \(p_2\) | Highest pressure at the tank (absolute, below the relief setting) | Pa |
| \(\alpha\) | Linear expansion coefficient of the piping | 1/K |
| \(v_1\) | Specific volume at the fill temperature | m³/kg |
| \(v_2\) | Specific volume at the highest temperature | m³/kg |
| \(V_e\) | Net expansion volume | m³ |
| \(V_t\) | Tank volume | m³ |
Method and standards
Volume balance and Boyle's law.
Where it is used
- Chilled and hot water systems.
- Closed cooling water circuits.
Common mistakes
- Gauge pressures in the ratio.
- Fill temperature too high.
Assumptions and limits
- Diaphragm tank, isothermal gas.
References
- Water expansion from IAPWS-IF97 specific volumes less pipe expansion 3αΔT; diaphragm tank by Boyle's law V_t = V_e/(1 − p₁/p₂) (ASHRAE Handbook—HVAC Systems and Equipment, hydronic systems)
Questions and answers
5 m³ heated from 10 °C to 90 °C, 2.5 to 5 bar(a)?
The water expands about 3.6 %, less 0.3 % for the pipes: about 164 L net and a 328 L tank.
Why absolute pressures?
Boyle's law works on absolute pressure.
Chilled water systems?
Use the highest ambient the idle system can reach as the highest temperature.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.