Expansion Tank for a Closed Water System (Diaphragm)

Size of a diaphragm expansion tank for a closed chilled or hot water system from system volume, fill and maximum temperatures and the pressures (water from IF97).

Refinery and petrochemicalChemical and fertiliserFood, dairy and textileIAPWS-IF97 (water and steam)

Inputs

Examples: Hot water 5 m³, 10 to 90 °CChilled water 20 m³, 7 to 40 °C idleNo pipe expansion

Carbon steel about 11.7 × 10⁻⁶ /K; 0 to ignore.

Results

Water specific volumes at the highest pressure (IAPWS-IF97); the gas side follows Boyle's law at constant temperature.

Specific volume at the fill temperature9.9985e-04m³/kg
Specific volume at the highest temperature0.001008m³/kg
Net expansion volume132.08L
Tank volume264.17L

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Hot water 5 m³, 10 to 90 °C. The inputs, in the units selected above:

InputValue
System water volume5.0000 m³
Fill (lowest) temperature10.000 °C
Highest temperature90.000 °C
Pre-charge or fill pressure at the tank (absolute)2.5000 bar
Highest pressure at the tank (absolute, below the relief setting)5.0000 bar
Linear expansion coefficient of the piping11.700 µm/(m·K)

Applying the formula below gives:

ResultValue
Specific volume at the fill temperature0.001000 m³/kg
Specific volume at the highest temperature0.001036 m³/kg
Net expansion volume164.06 L
Tank volume328.12 L

Open this example in the calculator and change any input.

Formula

\(V_e = V_s\left[\left(\frac{v_2}{v_1} - 1\right) - 3\alpha\Delta T\right], \quad V_t = \frac{V_e}{1 - p_1/p_2}\)

Variables

Symbol Meaning SI unit
\(V_s\) System water volume m³
\(T_1\) Fill (lowest) temperature K
\(T_2\) Highest temperature K
\(p_1\) Pre-charge or fill pressure at the tank (absolute) Pa
\(p_2\) Highest pressure at the tank (absolute, below the relief setting) Pa
\(\alpha\) Linear expansion coefficient of the piping 1/K
\(v_1\) Specific volume at the fill temperature m³/kg
\(v_2\) Specific volume at the highest temperature m³/kg
\(V_e\) Net expansion volume m³
\(V_t\) Tank volume m³

Method and standards

Volume balance and Boyle's law.

Where it is used

  • Chilled and hot water systems.
  • Closed cooling water circuits.

Common mistakes

  • Gauge pressures in the ratio.
  • Fill temperature too high.

Assumptions and limits

  • Diaphragm tank, isothermal gas.

References

  • Water expansion from IAPWS-IF97 specific volumes less pipe expansion 3αΔT; diaphragm tank by Boyle's law V_t = V_e/(1 − p₁/p₂) (ASHRAE Handbook—HVAC Systems and Equipment, hydronic systems)

Questions and answers

5 m³ heated from 10 °C to 90 °C, 2.5 to 5 bar(a)?

The water expands about 3.6 %, less 0.3 % for the pipes: about 164 L net and a 328 L tank.

Why absolute pressures?

Boyle's law works on absolute pressure.

Chilled water systems?

Use the highest ambient the idle system can reach as the highest temperature.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.