FireCADCalc

Chilled or Hot Water Energy (BTU Meter)

Cooling or heating power and energy from water flow and supply and return temperatures, as a BTU or energy meter computes it, with water from IF97.

Refinery and petrochemicalChemical and fertiliserFood, dairy and textileIAPWS-IF97 (water and steam)

Inputs

Examples: Chilled water 250 m³/h, 7/12.5 °CHot water 40 m³/h, 80/60 °C, meter on supply

Results

Density taken where the flow is measured; a meter must use matched temperature sensors, as small ΔT errors dominate.

Mass flow38.877t/h
Power904.50kW
Power in TR257.19TR
Energy over the time1,809.0MWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Chilled water 250 m³/h, 7/12.5 °C. The inputs, in the units selected above:

InputValue
Water flow (measured)250.00 m³/h
Supply temperature7.0000 °C
Return temperature12.500 °C
Flow meter locationReturn line
Operating time3,000.0 h
Line pressure (absolute)5.0000 bar

Applying the formula below gives:

ResultValue
Mass flow249.91 t/h
Power1,601.5 kW
Power in TR455.37 TR
Energy over the time4,804.4 MWh

Open this example in the calculator and change any input.

Formula

\(\dot Q = \rho \dot V\, |h(T_r) - h(T_s)|, \quad E = \dot Q\, t\)

Variables

Symbol Meaning SI unit
\(\dot V\) Water flow (measured) m³/s
\(T_s\) Supply temperature K
\(T_r\) Return temperature K
\(\text{meter}\) Flow meter location -
\(t\) Operating time s
\(p\) Line pressure (absolute) Pa
\(\dot m\) Mass flow kg/s
\(\dot Q\) Power W
\(\dot Q_{TR}\) Power in TR W
\(E\) Energy over the time J

Method and standards

Energy balance.

Where it is used

  • Chiller plant performance checks.
  • Billing tenants for chilled water.

Common mistakes

  • A fixed 4.186 kJ/kg K at hot water temperatures.
  • Unmatched sensors.

Assumptions and limits

  • Steady flow over the period.

References

  • Q = ρ V̇ (h_r − h_s) with IAPWS-IF97 density and enthalpy (EN 1434 heat meter principle)

Questions and answers

250 m³/h with 7 / 12.5 °C?

About 1,600 kW, roughly 455 TR.

Why does the meter location matter?

Density differs slightly between supply and return.

Biggest error source?

The temperature pair: 0.1 K error on 5.5 K is about 2 %.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.