Worked example
Example: Chilled water 250 m³/h, 7/12.5 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water flow (measured) | 250.00 m³/h |
| Supply temperature | 7.0000 °C |
| Return temperature | 12.500 °C |
| Flow meter location | Return line |
| Operating time | 3,000.0 h |
| Line pressure (absolute) | 5.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mass flow | 249.91 t/h |
| Power | 1,601.5 kW |
| Power in TR | 455.37 TR |
| Energy over the time | 4,804.4 MWh |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \rho \dot V\, |h(T_r) - h(T_s)|, \quad E = \dot Q\, t\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Water flow (measured) | m³/s |
| \(T_s\) | Supply temperature | K |
| \(T_r\) | Return temperature | K |
| \(\text{meter}\) | Flow meter location | - |
| \(t\) | Operating time | s |
| \(p\) | Line pressure (absolute) | Pa |
| \(\dot m\) | Mass flow | kg/s |
| \(\dot Q\) | Power | W |
| \(\dot Q_{TR}\) | Power in TR | W |
| \(E\) | Energy over the time | J |
Method and standards
Energy balance.
Where it is used
- Chiller plant performance checks.
- Billing tenants for chilled water.
Common mistakes
- A fixed 4.186 kJ/kg K at hot water temperatures.
- Unmatched sensors.
Assumptions and limits
- Steady flow over the period.
References
- Q = ρ V̇ (h_r − h_s) with IAPWS-IF97 density and enthalpy (EN 1434 heat meter principle)
Questions and answers
250 m³/h with 7 / 12.5 °C?
About 1,600 kW, roughly 455 TR.
Why does the meter location matter?
Density differs slightly between supply and return.
Biggest error source?
The temperature pair: 0.1 K error on 5.5 K is about 2 %.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.