Absorption Chiller: Steam or Heat Input for a Cooling Load

Heat input and steam consumption of a single- or double-effect absorption chiller from the cooling capacity, its COP and the steam pressure (IF97).

Process steam and utilitiesSugar mill and cogenerationFood, dairy and textileIAPWS-IF97 (water and steam)

Inputs

Examples: 300 TR double-effect, 9 bar(a)150 TR single-effect, 2 bar(a)

About 0.7 for single-effect, 1.2–1.4 for double-effect; from the maker.

Results

Dry saturated steam assumed; wet steam gives less heat per kg. A tower for an absorption chiller rejects much more heat than for an electric chiller.

Heat input to the generator811.58kW
Heat given up per kg of steam2,395.4kJ/kg
Steam consumption1,219.7kg/h
Steam per TR4.0657kg/h
Heat rejected to the cooling tower1,866.6kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 300 TR double-effect, 9 bar(a). The inputs, in the units selected above:

InputValue
Cooling capacity300.00 TR
Thermal COP1.3000 -
Steam pressure (absolute)9.0000 bar
Condensate leaving temperature90.000 °C

Applying the formula below gives:

ResultValue
Heat input to the generator811.58 kW
Heat given up per kg of steam2,395.4 kJ/kg
Steam consumption1,219.7 kg/h
Steam per TR4.0657 kg/h
Heat rejected to the cooling tower1,866.6 kW

Open this example in the calculator and change any input.

Formula

\(\dot Q_g = \frac{\dot Q_e}{COP}, \quad \dot m_s = \frac{\dot Q_g}{h_g(p_s) - h(p_s, T_c)}, \quad \dot Q_r = \dot Q_e + \dot Q_g\)

Variables

Symbol Meaning SI unit
\(\dot Q_e\) Cooling capacity W
\(COP\) Thermal COP -
\(p_s\) Steam pressure (absolute) Pa
\(T_c\) Condensate leaving temperature K
\(\dot Q_g\) Heat input to the generator W
\(\Delta h\) Heat given up per kg of steam J/kg
\(\dot m_s\) Steam consumption kg/s
\(\dot m_s/TR\) Steam per TR kg/s
\(\dot Q_r\) Heat rejected to the cooling tower W

Method and standards

Energy balance.

Where it is used

  • Trigeneration and cogeneration plants.
  • Sugar and process plants with spare steam.

Common mistakes

  • Single-effect COP for double-effect.
  • Ignoring condensate sub-cooling.

Assumptions and limits

  • Dry saturated steam at p_s; superheated or wet supply steam is not an input (wet steam gives less heat per kg).
  • The heat rejected is cooling plus heat input; the solution pump power, which also ends up in the tower, is left out.

References

  • Energy balance Q_g = Q_e/COP; steam and condensate enthalpies from IAPWS-IF97

Questions and answers

300 TR double-effect, COP 1.3, 9 bar(a) steam?

About 810 kW of heat: roughly 1,220 kg/h of steam, about 4.1 kg/h per TR.

Why use one?

Where waste or extraction steam is cheap, or electricity is short.

Cooling tower?

Rejects cooling plus heat input: about 1.8 times the cooling here.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.