Worked example
Example: 300 TR double-effect, 9 bar(a). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cooling capacity | 300.00 TR |
| Thermal COP | 1.3000 - |
| Steam pressure (absolute) | 9.0000 bar |
| Condensate leaving temperature | 90.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat input to the generator | 811.58 kW |
| Heat given up per kg of steam | 2,395.4 kJ/kg |
| Steam consumption | 1,219.7 kg/h |
| Steam per TR | 4.0657 kg/h |
| Heat rejected to the cooling tower | 1,866.6 kW |
Open this example in the calculator and change any input.
Formula
\(\dot Q_g = \frac{\dot Q_e}{COP}, \quad \dot m_s = \frac{\dot Q_g}{h_g(p_s) - h(p_s, T_c)}, \quad \dot Q_r = \dot Q_e + \dot Q_g\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q_e\) | Cooling capacity | W |
| \(COP\) | Thermal COP | - |
| \(p_s\) | Steam pressure (absolute) | Pa |
| \(T_c\) | Condensate leaving temperature | K |
| \(\dot Q_g\) | Heat input to the generator | W |
| \(\Delta h\) | Heat given up per kg of steam | J/kg |
| \(\dot m_s\) | Steam consumption | kg/s |
| \(\dot m_s/TR\) | Steam per TR | kg/s |
| \(\dot Q_r\) | Heat rejected to the cooling tower | W |
Method and standards
Energy balance.
Where it is used
- Trigeneration and cogeneration plants.
- Sugar and process plants with spare steam.
Common mistakes
- Single-effect COP for double-effect.
- Ignoring condensate sub-cooling.
Assumptions and limits
- Dry saturated steam at p_s; superheated or wet supply steam is not an input (wet steam gives less heat per kg).
- The heat rejected is cooling plus heat input; the solution pump power, which also ends up in the tower, is left out.
References
- Energy balance Q_g = Q_e/COP; steam and condensate enthalpies from IAPWS-IF97
Questions and answers
300 TR double-effect, COP 1.3, 9 bar(a) steam?
About 810 kW of heat: roughly 1,220 kg/h of steam, about 4.1 kg/h per TR.
Why use one?
Where waste or extraction steam is cheap, or electricity is short.
Cooling tower?
Rejects cooling plus heat input: about 1.8 times the cooling here.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.