Solar Air Heater (Air Under the Absorber): F′, F_R, Outlet Temperature

Useful gain, outlet air temperature and efficiency of a covered solar air heater with the air flowing in a duct behind the absorber, in common practice.

Food, dairy and textile

Inputs

Examples: Crop dryer collector: 2 m x 6 m, 50 mm channel, 0.15 kg/s, ambient inletLow flow, laminar channel: 1 m x 2 m, 0.01 kg/s

Accepted: 0.1 to 20 m
Accepted: 0.2 to 50 m
Accepted: 2 to 300 mm
Accepted: 1 to 1,400 W/m²
Accepted: 10 to 100 %
Accepted: 0.5 to 30 W/(m²·K)
Accepted: 0 to 10 W/(m²·K)
Accepted: 2 to 100 %
Accepted: 2 to 100 %
Accepted: -53.15 to 126.85 °C
Accepted: -53.15 to 56.85 °C
Accepted: 0.36 to 72,000 kg/h
Accepted: 0.95 to 1.1 kJ/(kg·K)
Accepted: 0.015 to 0.05 W/(m·K)
Accepted: 0.01 to 0.04 mPa·s

Results

Type (b) air heater: air flows between the absorber and an insulated back plate, with radiation between them; U_t should be taken at the mean absorber temperature (repeat with a new U_t if T_pm differs much from the value assumed).

Turbulent duct flow: Nu = 0.0158 Re^0.8 (fully developed, one side heated).

Overall loss coefficient U_t + U_b6.3000W/(m²·K)
Duct Reynolds number8,064.5
Air-side coefficient (each duct wall)5.5868W/(m²·K)
Radiation coefficient across the duct5.8790W/(m²·K)
Collector efficiency factor57.292%
Collector flow factor86.940%
Heat removal factor49.810%
Useful gain3,825.4W
Outlet air temperature55.325°C
Collector efficiency39.848%
Mean air temperature43.267°C
Mean absorber temperature80.987°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Crop dryer collector: 2 m x 6 m, 50 mm channel, 0.15 kg/s, ambient inlet. The inputs, in the units selected above:

InputValue
Collector width2.0000 m
Collector length (flow direction)6.0000 m
Air channel depth50.000 mm
Radiation on the collector800.00 W/m²
Effective transmittance–absorptance product80.000 %
Top loss coefficient5.5000 W/(m²·K)
Back and edge loss coefficient0.80000 W/(m²·K)
Emittance of the absorber underside90.000 %
Emittance of the duct back plate90.000 %
Inlet air temperature30.000 °C
Ambient temperature30.000 °C
Air mass flow540.00 kg/h
Air specific heat1.0070 kJ/(kg·K)
Air thermal conductivity0.026500 W/(m·K)
Air viscosity0.018600 mPa·s

Applying the formula below gives:

ResultValue
Overall loss coefficient U_t + U_b6.3000 W/(m²·K)
Duct Reynolds number8,064.5
Air-side coefficient (each duct wall)5.5868 W/(m²·K)
Radiation coefficient across the duct5.8790 W/(m²·K)
Collector efficiency factor57.292 %
Collector flow factor86.940 %
Heat removal factor49.810 %
Useful gain3,825.4 W
Outlet air temperature55.325 °C
Collector efficiency39.848 %
Mean air temperature43.267 °C
Mean absorber temperature80.987 °C

Open this example in the calculator and change any input.

Formula

\(F' = \left[1 + \frac{U_L}{h + \left(1/h + 1/h_r\right)^{-1}}\right]^{-1}, \quad h_r = \frac{4\sigma\bar T^3}{1/\varepsilon_1 + 1/\varepsilon_2 - 1}\)

\(F_R = F'F'', \quad F'' = \frac{\dot mc_p}{A_cU_LF'}\left[1 - e^{-A_cU_LF'/(\dot mc_p)}\right], \quad Q_u = A_cF_R\left[G_T(\tau\alpha) - U_L(T_i - T_a)\right]\)

Variables

Symbol Meaning SI unit
\(W\) Collector width m
\(L\) Collector length (flow direction) m
\(d\) Air channel depth m
\(G_T\) Radiation on the collector W/m²
\((\tau\alpha)\) Effective transmittance–absorptance product -
\(U_t\) Top loss coefficient W/(m²·K)
\(U_b\) Back and edge loss coefficient W/(m²·K)
\(\varepsilon_1\) Emittance of the absorber underside -
\(\varepsilon_2\) Emittance of the duct back plate -
\(T_i\) Inlet air temperature K
\(T_a\) Ambient temperature K
\(\dot m\) Air mass flow kg/s
\(c_p\) Air specific heat J/(kg·K)
\(k\) Air thermal conductivity W/(m·K)
\(\mu\) Air viscosity Pa·s
\(U_L\) Overall loss coefficient U_t + U_b W/(m²·K)
\(Re\) Duct Reynolds number -
\(h\) Air-side coefficient (each duct wall) W/(m²·K)
\(h_r\) Radiation coefficient across the duct W/(m²·K)
\(F'\) Collector efficiency factor -
\(F''\) Collector flow factor -
\(F_R\) Heat removal factor -
\(Q_u\) Useful gain W
\(T_o\) Outlet air temperature K
\(\eta\) Collector efficiency -
\(T_{fm}\) Mean air temperature K
\(T_{pm}\) Mean absorber temperature K

Method and standards

Hottel–Whillier analysis of an air heater with the duct behind the absorber.

Where it is used

  • Solar crop and timber dryers.
  • Space-heating air collectors.
  • Process air preheating.

Common mistakes

  • Using the water-collector F′ formula.
  • Ignoring radiation between absorber and back plate.

Assumptions and limits

  • Steady state; uniform flow; U_t entered for the absorber temperature.

Questions and answers

Why is the radiation coefficient in F′?

The absorber also heats the back plate by radiation, and the back plate passes that heat to the air, so the air sees an extra parallel path.

Why are air heaters less efficient than water collectors?

Air-side coefficients are low (tens of W/(m²·K)), which lowers F′ and so F_R.

What do the defaults represent?

An illustrative case: Crop dryer collector: 2 m x 6 m, 50 mm channel, 0.15 kg/s, ambient inlet. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), sec. 6.14, Fig. 6.14.1(b) and Example 6.14.1

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.