Worked example
Example: Aluminium fin 0.4 mm, 100 mm pitch, bond 30 W/(m K), 2.5 m2, 0.02 kg/s. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Overall loss coefficient | 4.5000 W/(m²·K) |
| Tube spacing | 100.00 mm |
| Tube outside diameter | 12.000 mm |
| Tube inside diameter | 10.000 mm |
| Plate (fin) thickness | 0.40000 mm |
| Plate conductivity (copper 385, aluminium 211) | 211.00 W/(m·K) |
| Bond conductance per unit length (0 = perfect bond) | 30.000 W/m |
| Heat transfer coefficient inside the tubes | 1,000.0 W/(m²·K) |
| Collector area | 2.5000 m² |
| Fluid flow through the collector | 0.020000 kg/s |
| Fluid specific heat | 4.1800 kJ/(kg·K) |
| Absorbed solar radiation per unit area | 700.00 W/m² |
| Incident radiation on the collector (for efficiency) | 900.00 W/m² |
| Fluid inlet temperature | 50.000 °C |
| Ambient temperature | 25.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fin parameter | 7.3019 1/m |
| Fin efficiency | 96.696 % |
| Collector efficiency factor | 94.404 % |
| Collector flow factor | 93.909 % |
| Heat removal factor | 88.654 % |
| Useful gain | 1,302.1 W |
| Useful gain per unit area | 520.84 W/m² |
| Outlet temperature | 65.575 °C |
| Collector efficiency | 57.871 % |
Open this example in the calculator and change any input.
Formula
\(F = \frac{\tanh[m(W - D)/2]}{m(W - D)/2}, \quad m = \sqrt{\frac{U_L}{k\delta}}, \quad F' = \frac{1/U_L}{W\left[\frac{1}{U_L[D + (W - D)F]} + \frac{1}{C_b} + \frac{1}{\pi D_ih_{fi}}\right]}\)
\(F_R = F'F'' = \frac{\dot mc_p}{A_cU_L}\left[1 - \exp\left(-\frac{A_cU_LF'}{\dot mc_p}\right)\right], \quad Q_u = A_cF_R[S - U_L(T_i - T_a)]\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(U_L\) | Overall loss coefficient | W/(m²·K) |
| \(W\) | Tube spacing | m |
| \(D\) | Tube outside diameter | m |
| \(D_i\) | Tube inside diameter | m |
| \(\delta\) | Plate (fin) thickness | m |
| \(k\) | Plate conductivity (copper 385, aluminium 211) | W/(m·K) |
| \(C_b\) | Bond conductance per unit length (0 = perfect bond) | W/m |
| \(h_{fi}\) | Heat transfer coefficient inside the tubes | W/(m²·K) |
| \(A_c\) | Collector area | m² |
| \(\dot m\) | Fluid flow through the collector | kg/s |
| \(c_p\) | Fluid specific heat | J/(kg·K) |
| \(S\) | Absorbed solar radiation per unit area | W/m² |
| \(G_T\) | Incident radiation on the collector (for efficiency) | W/m² |
| \(T_i\) | Fluid inlet temperature | K |
| \(T_a\) | Ambient temperature | K |
| \(m\) | Fin parameter | 1/m |
| \(F\) | Fin efficiency | - |
| \(F'\) | Collector efficiency factor | - |
| \(F''\) | Collector flow factor | - |
| \(F_R\) | Heat removal factor | - |
| \(Q_u\) | Useful gain | W |
| \(q_u\) | Useful gain per unit area | W/m² |
| \(T_o\) | Outlet temperature | K |
| \(\eta\) | Collector efficiency | - |
Method and standards
Hottel–Whillier–Bliss flat-plate collector theory.
Where it is used
- Designing absorber plates and choosing flow rates.
- Hour-by-hour collector output in system studies.
Common mistakes
- Using G_T instead of the absorbed S = G_T(τα) in the gain equation.
- Using outlet or mean temperature where the equation needs the inlet temperature.
Assumptions and limits
- Steady state, uniform flow in parallel tubes, constant U_L.
Questions and answers
What does F_R mean physically?
It is the ratio of the actual useful gain to the gain if the whole absorber were at the fluid inlet temperature, the lowest-loss condition.
How do I raise F'?
Closer tube spacing, thicker or more conductive plate, a good bond and turbulent flow in the tubes; copper sheet 0.5 mm at 150 mm spacing gives about 0.84.
What do the defaults represent?
An illustrative case: Aluminium fin 0.4 mm, 100 mm pitch, bond 30 W/(m K), 2.5 m2, 0.02 kg/s. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), secs. 6.5 to 6.7, eqs. 6.5.12, 6.5.18, 6.7.5 and 6.7.6, Examples 6.5.1 and 6.7.1