Reactive Power Drawn by a Transformer

Reactive power a transformer draws from its no-load current, impedance voltage and loading, for sizing a fixed capacitor on the transformer.

Thermal power plantProcess steam and utilities

Inputs

Examples: 1 000 kVA, 1.2 % no-load current, 5 %, 70 % load2 500 kVA, 0.8 %, 6 %, full load315 kVA, 2 %, 4 %, no load

Results

A fixed capacitor on a transformer is usually sized near the no-load figure so that it never over-compensates at light load.

No-load reactive power i₀ S_r20.000kvar
Reactive power of the leakage reactance u_k a² S_r150.00kvar
Total reactive power drawn170.00kvar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 1 000 kVA, 1.2 % no-load current, 5 %, 70 % load. The inputs, in the units selected above:

InputValue
Transformer rating1,000.0 kVA
No-load (magnetising) current1.2000 %
Impedance voltage5.0000 %
Loading as a share of rating70.000 %

Applying the formula below gives:

ResultValue
No-load reactive power i₀ S_r12.000 kvar
Reactive power of the leakage reactance u_k a² S_r24.500 kvar
Total reactive power drawn36.500 kvar

Open this example in the calculator and change any input.

Formula

\(Q = i_0\, S_r + u_k\, a^2\, S_r\)

Variables

Symbol Meaning SI unit
\(S_r\) Transformer rating VA
\(i_0\) No-load (magnetising) current -
\(u_k\) Impedance voltage -
\(a\) Loading as a share of rating -
\(Q_0\) No-load reactive power i₀ S_r var
\(Q_L\) Reactive power of the leakage reactance u_k a² S_r var
\(Q\) Total reactive power drawn var

Method and standards

Magnetising branch plus series reactance.

Where it is used

  • High-voltage metered consumers.
  • Fixed compensation design.

Common mistakes

  • Using load losses instead of impedance.
  • Over-compensating at light load.

Assumptions and limits

  • Using u_k for the leakage reactance overstates Q_L by u_k/√(u_k² − u_r²): negligible for large transformers, a few per cent for small distribution transformers with a large resistive part u_r.

  • Reactance taken as the impedance voltage.

References

  • Q = i₀ S_r + u_k a² S_r (transformer equivalent circuit; IEC 60076 nameplate quantities)

Questions and answers

What does a 1000 kVA transformer with 1.2 % no-load current and 5 % impedance draw at 70 % load?

12 kvar magnetising plus 24.5 kvar in the leakage reactance: 36.5 kvar.

Why does it matter?

Metering on the high-voltage side sees this kvar even with perfect correction on the low-voltage side.

How much fixed capacitor?

About the no-load kvar.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.