Worked example
Example: 1 000 kVA, 1.2 % no-load current, 5 %, 70 % load. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Transformer rating | 1,000.0 kVA |
| No-load (magnetising) current | 1.2000 % |
| Impedance voltage | 5.0000 % |
| Loading as a share of rating | 70.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| No-load reactive power i₀ S_r | 12.000 kvar |
| Reactive power of the leakage reactance u_k a² S_r | 24.500 kvar |
| Total reactive power drawn | 36.500 kvar |
Open this example in the calculator and change any input.
Formula
\(Q = i_0\, S_r + u_k\, a^2\, S_r\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S_r\) | Transformer rating | VA |
| \(i_0\) | No-load (magnetising) current | - |
| \(u_k\) | Impedance voltage | - |
| \(a\) | Loading as a share of rating | - |
| \(Q_0\) | No-load reactive power i₀ S_r | var |
| \(Q_L\) | Reactive power of the leakage reactance u_k a² S_r | var |
| \(Q\) | Total reactive power drawn | var |
Method and standards
Magnetising branch plus series reactance.
Where it is used
- High-voltage metered consumers.
- Fixed compensation design.
Common mistakes
- Using load losses instead of impedance.
- Over-compensating at light load.
Assumptions and limits
Using u_k for the leakage reactance overstates Q_L by u_k/√(u_k² − u_r²): negligible for large transformers, a few per cent for small distribution transformers with a large resistive part u_r.
Reactance taken as the impedance voltage.
References
- Q = i₀ S_r + u_k a² S_r (transformer equivalent circuit; IEC 60076 nameplate quantities)
Questions and answers
What does a 1000 kVA transformer with 1.2 % no-load current and 5 % impedance draw at 70 % load?
12 kvar magnetising plus 24.5 kvar in the leakage reactance: 36.5 kvar.
Why does it matter?
Metering on the high-voltage side sees this kvar even with perfect correction on the low-voltage side.
How much fixed capacitor?
About the no-load kvar.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.