Worked example
Example: 1 000 kVA, 11 kV / 433 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated power | 1,000.0 kVA |
| Primary (HV) rated voltage, line to line | 11.000 kV |
| Secondary (LV) rated voltage, line to line | 433.00 V |
| System | Three-phase |
Applying the formula below gives:
| Result | Value |
|---|---|
| Primary rated current | 52.486 A |
| Secondary rated current | 1,333.4 A |
| Voltage ratio | 25.404 |
Open this example in the calculator and change any input.
Formula
\(I_1 = \frac{S_r}{\sqrt 3\,U_1} \qquad I_2 = \frac{S_r}{\sqrt 3\,U_2} \qquad \text{(single-phase: without } \sqrt 3\text{)} \qquad \text{ratio} = \frac{U_1}{U_2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S_r\) | rated power | VA |
| \(U_1\) | primary (HV) rated voltage, line to line | V |
| \(U_2\) | secondary (LV) rated voltage, line to line | V |
| \(\text{system}\) | three-phase or single-phase | – |
| \(I_1\) | primary rated current | A |
| \(I_2\) | secondary rated current | A |
| \(U_1/U_2\) | voltage ratio | – |
Method and standards
Rated current as defined in IEC 60076-1: the current flowing through a line terminal when rated power is applied at rated voltage.
Where it is used
- Sizing cables and protection for transformers.
- Checking transformer loading.
- Plant electrical design.
Common mistakes
- Using phase voltage instead of line voltage.
- Mixing kVA and kW.
- Using the wrong side's voltage.
Assumptions and limits
- Balanced three-phase or single-phase transformer; for a three-winding transformer apply it to each winding with its own rating.
- Rated (no-load) voltages; the current at a different operating voltage for the same kVA scales inversely.
References
- IEC 60076-1 (rated current)
Questions and answers
What is the full-load current of a 1 000 kVA transformer?
At 11 kV / 433 V, 52.5 A on the 11 kV side and 1 333 A on the 433 V side: I = S/(√3·U).
Why 433 V and not 415 V?
Distribution transformers are often rated at 433 V no-load so that the voltage at the load, after the drop, is about 415 V. Use the rated voltage on the nameplate.
Is this the current the transformer can carry?
It is the rated current, which the transformer carries continuously at rated conditions (IEC 60076-1). Overload capability depends on the loading guide and the ambient temperature.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.