Worked example
Example: 440 / 380 V, 50 kVA. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Higher voltage | 440.00 V |
| Lower voltage | 380.00 V |
| Throughput power (total for three phase) | 50.000 kVA |
| Supply | Single phase |
Applying the formula below gives:
| Result | Value |
|---|---|
| Current on the higher-voltage side (series winding) | 113.64 A |
| Current on the lower-voltage side | 131.58 A |
| Current in the common winding I₂ − I₁ | 17.943 A |
| Power transformed by induction | 6.8182 kVA |
| Power conducted directly | 43.182 kVA |
| Copper saved against a two-winding transformer V₂ / V₁ | 86.364 % |
Open this example in the calculator and change any input.
Formula
\(I_1 = \frac{S}{k_3V_1}, \quad I_2 = \frac{S}{k_3V_2}, \quad I_c = I_2 - I_1, \quad k_3 = 1\ (\text{single phase}),\ \sqrt3\ (\text{three phase})\)
\(S_t = S\left(1 - \frac{V_2}{V_1}\right), \quad S_c = S\, \frac{V_2}{V_1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_1\) | Higher voltage | V |
| \(V_2\) | Lower voltage | V |
| \(S\) | Throughput power (total for three phase) | VA |
| \(\text{phases}\) | Supply: single or three phase | - |
| \(k_3\) | 1 for single phase, √3 for three phase | - |
| \(I_1\) | Current on the higher-voltage side (series winding) | A |
| \(I_2\) | Current on the lower-voltage side | A |
| \(I_c\) | Current in the common winding I₂ − I₁ | A |
| \(S_t\) | Power transformed by induction | VA |
| \(S_c\) | Power conducted directly | VA |
| \(k\) | Copper saved against a two-winding transformer V₂ / V₁ | - |
Method and standards
Ideal autotransformer.
Where it is used
- Voltage correctors and starters.
- Electrical examinations.
Common mistakes
- Expecting isolation.
- Using it for large ratios (little saving).
Assumptions and limits
- Ideal. For three phase choose the three-phase supply and enter the total kVA and the line voltages; the currents are line (winding) currents of a star-connected autotransformer.
References
- Autotransformer theory (M.G. Say, Performance and Design of AC Machines)
Questions and answers
How much of 50 kVA does a 440/380 V autotransformer actually transform?
6.8 kVA; the other 43.2 kVA is conducted.
How much copper is saved?
V₂/V₁ = 86 % of a two-winding transformer's copper.
What is the catch?
No isolation between the two sides, and a higher fault level.