Autotransformer Currents, Transformed Power and Copper Saving

Currents in the series and common windings of a single-phase autotransformer, the power transformed and conducted, and the copper saved against two windings.

Thermal power plantProcess steam and utilities

Inputs

Examples: 440 / 380 V, 50 kVA415 / 240 V, 20 kVA11 / 6.6 kV, 1 MVAThree-phase 440 / 380 V line, 150 kVA total

Results

Current on the higher-voltage side (series winding)48.193A
Current on the lower-voltage side83.333A
Current in the common winding I₂ − I₁35.141A
Power transformed by induction8.4337kVA
Power conducted directly11.566kVA
Copper saved against a two-winding transformer V₂ / V₁57.831%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 440 / 380 V, 50 kVA. The inputs, in the units selected above:

InputValue
Higher voltage440.00 V
Lower voltage380.00 V
Throughput power (total for three phase)50.000 kVA
SupplySingle phase

Applying the formula below gives:

ResultValue
Current on the higher-voltage side (series winding)113.64 A
Current on the lower-voltage side131.58 A
Current in the common winding I₂ − I₁17.943 A
Power transformed by induction6.8182 kVA
Power conducted directly43.182 kVA
Copper saved against a two-winding transformer V₂ / V₁86.364 %

Open this example in the calculator and change any input.

Formula

\(I_1 = \frac{S}{k_3V_1}, \quad I_2 = \frac{S}{k_3V_2}, \quad I_c = I_2 - I_1, \quad k_3 = 1\ (\text{single phase}),\ \sqrt3\ (\text{three phase})\)

\(S_t = S\left(1 - \frac{V_2}{V_1}\right), \quad S_c = S\, \frac{V_2}{V_1}\)

Variables

Symbol Meaning SI unit
\(V_1\) Higher voltage V
\(V_2\) Lower voltage V
\(S\) Throughput power (total for three phase) VA
\(\text{phases}\) Supply: single or three phase -
\(k_3\) 1 for single phase, √3 for three phase -
\(I_1\) Current on the higher-voltage side (series winding) A
\(I_2\) Current on the lower-voltage side A
\(I_c\) Current in the common winding I₂ − I₁ A
\(S_t\) Power transformed by induction VA
\(S_c\) Power conducted directly VA
\(k\) Copper saved against a two-winding transformer V₂ / V₁ -

Method and standards

Ideal autotransformer.

Where it is used

  • Voltage correctors and starters.
  • Electrical examinations.

Common mistakes

  • Expecting isolation.
  • Using it for large ratios (little saving).

Assumptions and limits

  • Ideal. For three phase choose the three-phase supply and enter the total kVA and the line voltages; the currents are line (winding) currents of a star-connected autotransformer.

References

  • Autotransformer theory (M.G. Say, Performance and Design of AC Machines)

Questions and answers

How much of 50 kVA does a 440/380 V autotransformer actually transform?

6.8 kVA; the other 43.2 kVA is conducted.

How much copper is saved?

V₂/V₁ = 86 % of a two-winding transformer's copper.

What is the catch?

No isolation between the two sides, and a higher fault level.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.