Fault Level at an LV Bus by the MVA Method

Three-phase fault level and fault current at a bus fed through a transformer and cable from a grid of known fault level, with motor contribution, by the MVA method.

Thermal power plantProcess steam and utilitiesElectric motor

Inputs

Examples: 500 MVA grid, 2 MVA 6.25 % transformer, 415 V, 2 mΩ busduct, c = 1.1500 MVA grid, 2 MVA 6.25 % transformer, 415 V, 2 mΩ busduct, plain MVA (c = 1)250 MVA, 1.6 MVA 5 %, 433 V, no cable, 800 kVA motors at 0.2, c = 1.1250 MVA, 1.6 MVA 5 %, 433 V, no cable, 800 kVA motors at 0.2, plain MVA (c = 1)11 kV bus: 350 MVA grid, 10 MVA 8 %, 11 kV, 0.05 Ω cable, 3 MVA motors at 0.17, c = 1.111 kV bus: 350 MVA grid, 10 MVA 8 %, 11 kV, 0.05 Ω cable, 3 MVA motors at 0.17, plain MVA (c = 1)

From the motor maker; used only when motors are entered.
1.1 for the maximum fault current used to rate breakers and busbars (1.05 is allowed on LV systems with a +6 % voltage tolerance); 1.0 gives the plain MVA method.

Results

Impedances are added as magnitudes (no X/R angle), which gives a slightly lower current than a phasor sum when the X/R ratios differ; final equipment ratings need an IEC 60909 or IEEE study with X/R and peak current.

Fault level at the bus32.369MVA
Symmetrical fault current at the bus43.160kA
Fault level from the supply path alone28.369MVA
Motor contribution to the fault current5.3335kA

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 500 MVA grid, 2 MVA 6.25 % transformer, 415 V, 2 mΩ busduct, c = 1.1. The inputs, in the units selected above:

InputValue
Fault level of the supply at the transformer primary500.00 MVA
Transformer rating2.0000 MVA
Transformer impedance6.2500 %
Bus voltage (line to line)415.00 V
Impedance of the cable or busduct to the bus (0 = none)0.002000 Ω
Running motors at the bus (total kVA, 0 = none)0 kVA
Motor subtransient reactance20.000 %
Voltage factor c (IEC 60909)1.1000 -

Applying the formula below gives:

ResultValue
Fault level at the bus24.519 MVA
Symmetrical fault current at the bus34.111 kA
Fault level from the supply path alone24.519 MVA
Motor contribution to the fault current0 kA

Open this example in the calculator and change any input.

Formula

\(\frac{1}{S_{net}} = \frac{1}{S_g} + \frac{z_t}{S_t} + \frac{Z_c}{U^2}\)

\(S_f = c \left( S_{net} + \frac{S_m}{x_m} \right)\)

\(I_f = \frac{S_f}{\sqrt{3}\, U}, \quad I_m = \frac{c\, S_m / x_m}{\sqrt{3}\, U}\)

Variables

Symbol Meaning SI unit
\(S_g\) fault level of the supply VA
\(S_t\) transformer rating VA
\(z_t\) transformer impedance -
\(U\) bus voltage V
\(Z_c\) cable or busduct impedance Ω
\(S_m\) running motors at the bus VA
\(x_m\) motor subtransient reactance -
\(c\) voltage factor (IEC 60909) -
\(S_f\) fault level at the bus VA
\(I_f\) fault current A
\(S_{net}\) fault level from the supply path (the output is multiplied by c) VA
\(I_m\) motor contribution A

Method and standards

The MVA method: each component's short-circuit MVA is its rating divided by its per-unit impedance, or U²/Z for a cable. Series elements combine as reciprocals; motors feeding the fault add in parallel. Impedances are combined as magnitudes. A magnitude sum is never smaller than the phasor sum, so when the X/R ratios of grid, transformer and cable differ the current comes out somewhat low, not high. The result is multiplied by the voltage factor c of IEC 60909 (c_max = 1.1 for the maximum fault current), as a short-circuit study would apply it to the equivalent source.

Where it is used

  • Checking breaker and busbar fault ratings.
  • Estimating the effect of a larger transformer or a new motor load.
  • Quick checks before a full short-circuit study.

Common mistakes

  • Forgetting motor contribution on buses with large motor loads.
  • Using the grid's MVA at a different voltage level without the upstream impedance.
  • Treating the result as the peak (asymmetrical) current.

Assumptions and limits

  • Symmetrical three-phase fault; voltage factor c applied to all sources; no X/R angle.
  • Motor contribution is the initial subtransient value.

References

  • MVA method of short-circuit calculation

Questions and answers

What is the fault level at the LV side of a 2 MVA, 6.25 % transformer?

Fed from a 500 MVA grid through 2 mΩ of busduct, about 24.5 MVA, or 34 kA at 415 V, with the voltage factor c = 1.1 (22.3 MVA and 31 kA without it).

How does the MVA method work?

Each element gets a short-circuit MVA (rating ÷ impedance, or V²/Z); elements in series combine like resistors in parallel, and parallel sources such as motors simply add.

Is this good enough for breaker ratings?

For a first check, with c = 1.1, yes. Adding impedances as magnitudes gives a slightly low current when the X/R ratios differ, so leave margin; final ratings need an IEC 60909 or IEEE study with X/R ratios and peak current.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.