Worked example
Example: 500 MVA grid, 2 MVA 6.25 % transformer, 415 V, 2 mΩ busduct, c = 1.1. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fault level of the supply at the transformer primary | 500.00 MVA |
| Transformer rating | 2.0000 MVA |
| Transformer impedance | 6.2500 % |
| Bus voltage (line to line) | 415.00 V |
| Impedance of the cable or busduct to the bus (0 = none) | 0.002000 Ω |
| Running motors at the bus (total kVA, 0 = none) | 0 kVA |
| Motor subtransient reactance | 20.000 % |
| Voltage factor c (IEC 60909) | 1.1000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fault level at the bus | 24.519 MVA |
| Symmetrical fault current at the bus | 34.111 kA |
| Fault level from the supply path alone | 24.519 MVA |
| Motor contribution to the fault current | 0 kA |
Open this example in the calculator and change any input.
Formula
\(\frac{1}{S_{net}} = \frac{1}{S_g} + \frac{z_t}{S_t} + \frac{Z_c}{U^2}\)
\(S_f = c \left( S_{net} + \frac{S_m}{x_m} \right)\)
\(I_f = \frac{S_f}{\sqrt{3}\, U}, \quad I_m = \frac{c\, S_m / x_m}{\sqrt{3}\, U}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S_g\) | fault level of the supply | VA |
| \(S_t\) | transformer rating | VA |
| \(z_t\) | transformer impedance | - |
| \(U\) | bus voltage | V |
| \(Z_c\) | cable or busduct impedance | Ω |
| \(S_m\) | running motors at the bus | VA |
| \(x_m\) | motor subtransient reactance | - |
| \(c\) | voltage factor (IEC 60909) | - |
| \(S_f\) | fault level at the bus | VA |
| \(I_f\) | fault current | A |
| \(S_{net}\) | fault level from the supply path (the output is multiplied by c) | VA |
| \(I_m\) | motor contribution | A |
Method and standards
The MVA method: each component's short-circuit MVA is its rating divided by its per-unit impedance, or U²/Z for a cable. Series elements combine as reciprocals; motors feeding the fault add in parallel. Impedances are combined as magnitudes. A magnitude sum is never smaller than the phasor sum, so when the X/R ratios of grid, transformer and cable differ the current comes out somewhat low, not high. The result is multiplied by the voltage factor c of IEC 60909 (c_max = 1.1 for the maximum fault current), as a short-circuit study would apply it to the equivalent source.
Where it is used
- Checking breaker and busbar fault ratings.
- Estimating the effect of a larger transformer or a new motor load.
- Quick checks before a full short-circuit study.
Common mistakes
- Forgetting motor contribution on buses with large motor loads.
- Using the grid's MVA at a different voltage level without the upstream impedance.
- Treating the result as the peak (asymmetrical) current.
Assumptions and limits
- Symmetrical three-phase fault; voltage factor c applied to all sources; no X/R angle.
- Motor contribution is the initial subtransient value.
References
- MVA method of short-circuit calculation
Questions and answers
What is the fault level at the LV side of a 2 MVA, 6.25 % transformer?
Fed from a 500 MVA grid through 2 mΩ of busduct, about 24.5 MVA, or 34 kA at 415 V, with the voltage factor c = 1.1 (22.3 MVA and 31 kA without it).
How does the MVA method work?
Each element gets a short-circuit MVA (rating ÷ impedance, or V²/Z); elements in series combine like resistors in parallel, and parallel sources such as motors simply add.
Is this good enough for breaker ratings?
For a first check, with c = 1.1, yes. Adding impedances as magnitudes gives a slightly low current when the X/R ratios differ, so leave margin; final ratings need an IEC 60909 or IEEE study with X/R ratios and peak current.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.